Date Text
2006-04-04 00:00:00 
 1) SUBMIT A DETAIL UL ASSEMBLY DRAWING
 FOR THE ONE HOUR RATED WALL. THE
 INFORMATION SUBMITTED IS INADEQUATE.
  
 2) ON SHEET #5 WHAT TYPE OF FIRE
 BLOCKING MATERIALS WILL BE USED AT THE
 FLOORS AND CEILINGS. STATE THIS
 INFORMATION ON THE DRAWINGS. IN
 REFERENCE TO THE STATEMENT "FIRE RATED
 INSULATION AS PER CODES" EXPLAIN WHERE
 AND HOW THE INSULATION WILL BE
 INSTALLED. SAYING AS PER CODE IS NOT
 SUFFICENT INFORMATION. SEE NOTES FROM
 ELECTRIACAL REVIEWER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER