Plan Review Notes For Permit 06010186 |
Permit Number |
06010186 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-20 00:00:00 | 1) DUE TO THE FACT THAT EACH UNIT HAS | | ITS' OWN PCN NUMBER AND WILL NEED REPAIR | | WORK , A SEPERATE PERMIT APPLICATION HAS | | TO BE FILED FOR EACH UNIT. THIS IS BASE | | ON THE DESCRIPTION OF THE WORK | | SUBMITTED. IF THIS APPLICATION IS FOR | | THE WORK IN THE COMMON AREA ONLY, THE | | DESCRIPTION ON THE APPLICATION AND THE | | SCOPE OF WORK WILL HAVE TO BE ALTERED. | | | | 2) SUBMIT A DETAIL DRAWING SHOWING THE | | AREA WHERE THE WORK WILL BE DONE. ALL | | DRAWINGS AND DATA PRREPARED BY AN | | ARCHITECT OR ENGINEER SHALL BE AFFIXED | | WITH THEIR OFFICIAL SEAL, SIGNATURE AND | | DATE AS STATE LAW REQUIRES. | | WPB AMENDMENTS 106.1.2 SEE SECTION 106 | | FOR ADDITIONAL INFORMATION. | | | | 3) NOTE: IF SMOKE TRAVEL THROUGH THE A/C | | SYSTEM A MECHINICAL INSPECTOR WILL HAVE | | TO DO A PRE-INSPECT TO MAKE SURE THE A/C | | SYSTEM IS OK. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 |
|