2006-02-01 00:00:00 | |
| |
| DENIED |
| |
| |
| 1) CONTRACTOR SHALL SUBMIT 2 COPIES OF |
| THE FLORIDA STATE COVER SHEET WITH STATE |
| APPROVAL AND FL# AS PART OF THE PRODUCT |
| APPROVALS |
| |
| A) W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 2) CONTRACTOR SHALL SPECIFY THE SYSTEM |
| TO BE USED IN THE NOA. SPECIFY BUY |
| MARKING THE GLASS TYPE,ANCHOR OPTION,ETC |
| THAT WILL BE USED AND WILL COMPLY WITH |
| THE ENGINEERED WIND LOADS ON DRAWINGS |
| |
| 3) IF A DESIGN PROFESSIONAL REGISTERED |
| TO PRACTICE UNDER CHAPTER 481 OR 471 OF |
| THE FLORIDA STATUTES THEN HE OR SHE |
| SHALL AFFIX THEIR OFFICIAL SEAL, |
| SIGNATURE AND DATE TO SAID DRAWINGS AND |
| SPECIFICATIONS PER 106 FBC 2004 |
| |
| 4) AN ENGINEER PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS SHALL |
| INDICATE THEIR NAME AND LICENCE #, AS |
| WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| OF AUTHORIZATION #ON EACH SHEET PER |
| 61G15-23.002 (1)-(5) |
| |
| 5) ADD NOTE ON GLASS CONTRACTORS |
| DRAWINGS, ALUMINUM CONTACTING METALSTHAT |
| ARE NOT COMPATIBLE SHALL BE PROTECTED |
| PER 2003.8.4 FBC 2004 |
| |
| |
| |
| |
| BLDG PLAN REVIEW |