Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop E
Sequence Number 9
Notes
Date Text
2007-09-13 14:00:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} 210.52(B)(1) SMALL APPLIANCES
 RECEPTACLE OUTLETS SERVED IN THE KITCHEN, PANTRY,
 BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF A
 DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT.
 210.52(B)(2) NO OTHER OUTLETS THE TWO OR MORE
 SMALL-APPLIANCE BRANCH CIRCUITS SPECIFIED IN
 210.52(B)(1) SHALL HAVE NO OTHER OUTLETS. SEE PANEL
 SCHEDULE A CIRCUITS 18 AND 19 ARE IN VIOLATION OF THESE
 ARTICLES. THE DEVICES WERE NOT CIRCUITED ON PREVIOUS
 PLANS. THE LIGHTS MAY NOT BE ON THOSE CIRCUITS EITHER.
  
 2} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 CIRCUIT A-21. THE MEDIA AND POWDER ROOM BATHS AREN?T
 MARKED, BUT DON?T APPEAR ON SEPARATE CIRCUITS IN THE
 SCHEDULES. ?HIS? BATH ON THE SECOND FLOOR IS ALSO IN
 VIOLATION AS IT SHARES LIGHTS AND RECEPTACLES IN THE
 COMMON HALL.
  
 3} 110.26 THE POOL PUMP AND ACU #1 DISCONNECTS DO NOT
 SEEM TO HAVE THE REQUIRED CLEARANCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH [email protected]
 ELECTRICAL PLANS EXAMINER 561/805-6718
 CITY OF WEST PALM BEACH