Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop E
Sequence Number 7
Notes
Date Text
2006-08-11 00:00:00*** REDLINED THE FOLLOWING**
  
  
 PLEASE SEE MISSING EGRESS LT FIXTURE
 REQUIRED IN FOYER AREA FOR EGRESS FROM
 SEC FLR TO FIRST FLR AND 1ST FLR TO 2ND
 FLR. SOME SORT OF LT FIXTURE WILL BE
 REQUIRED. 210.70, LS 101 7.8
  
 PLEASE SE LOAD CALCULATIONS SHOW
 2-GARAGE DOOR OPENER CIRCUITS, HOWEVER
 PANEL SCHEDULE MENTIONS "'S" TWO YET
 ONLY IN ONE SPACE.
  
 THE ABOVE MAY BE REVISED WHEN PLANS ARE
 REVISED FOR ANY OTHER ITEMS BEFORE
 ROUGH.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  