2007-05-16 09:58:55REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) ROOMS ARE SHOWING AS BOXES WITH NO DOORS, PLEASE
 SUBMIT PLANS THAT SHOW ROOMS WITH DOORS, HALLWAYS ETC,
 AND LABEL ROOMS (BEDROOM, LIVING ROOM, KITCHEN, ETC).
  
 3) PLEASE SHOW AN A/C EQUIPMENT LISTING WITH ALL
 PERTINENT INFORMATION ON PLANS.
  
 4) PLEASE LABEL SECOND FLOOR.
  
 5) PLEASE SHOW ALL GAS APPLIANCES ON PLANS AND SHOW HOW
 THEY GETTING COMBUSTION AIR AND MAKE UP AIR, SEE 2004
 FBC/R M1701.
  
 6) PLEASE STATE ON PLANS WHICH AIR HANDLERS ARE IN THE
 ATTIC.
  
 7) PROVIDE RETURN AIR FOR BEDROOM #2, SEE 2004 FBC/R
 M1602.4.
  
 8) SEE YELLOW HIGH LIGHTED SUPPLY AIR DUCTS ON
 MECHANICAL PLANS, PLEASE SHOW SIZE OF DUCTS.
  
 9) SHOW LOCATION OF A/C CONDENSER UNITS ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.