Plan Review Notes For Permit 06010171 |
Permit Number |
06010171 |
|
Review Stop |
M |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2007-05-16 09:58:55 | REVISION TO MECHANICAL PLANS | | *** DENIED *** | | 1) INFORMATION MISSING FROM TITLE BLOCK. | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | 2) ROOMS ARE SHOWING AS BOXES WITH NO DOORS, PLEASE | | SUBMIT PLANS THAT SHOW ROOMS WITH DOORS, HALLWAYS ETC, | | AND LABEL ROOMS (BEDROOM, LIVING ROOM, KITCHEN, ETC). | | | | 3) PLEASE SHOW AN A/C EQUIPMENT LISTING WITH ALL | | PERTINENT INFORMATION ON PLANS. | | | | 4) PLEASE LABEL SECOND FLOOR. | | | | 5) PLEASE SHOW ALL GAS APPLIANCES ON PLANS AND SHOW HOW | | THEY GETTING COMBUSTION AIR AND MAKE UP AIR, SEE 2004 | | FBC/R M1701. | | | | 6) PLEASE STATE ON PLANS WHICH AIR HANDLERS ARE IN THE | | ATTIC. | | | | 7) PROVIDE RETURN AIR FOR BEDROOM #2, SEE 2004 FBC/R | | M1602.4. | | | | 8) SEE YELLOW HIGH LIGHTED SUPPLY AIR DUCTS ON | | MECHANICAL PLANS, PLEASE SHOW SIZE OF DUCTS. | | | | 9) SHOW LOCATION OF A/C CONDENSER UNITS ON PLANS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|