Date |
Text |
2006-07-25 00:00:00 | *********** UNSAT 5TH REVIEW ********* |
| |
| ** PLEAS SEE THIS IS THE 5TH REVIEW. |
| PLEASE SEE SOME COMMENTS BELOW ARE STILL |
| IN NEED OF BEING ADDRESSED FROM PREVIOUS |
| REVIEWS AND PLEASE SEE SOME NEW |
| COMMENTS. |
| |
| |
| 1) NOTE: PLEASE SEE SERVICE RISER IS |
| STILL VERY UNCLEAR AS THE 100A MCB SUB |
| PANEL IS NOT FED FROM ANYWHERE? PLEASE |
| SEE RISER SHOWS THIS PANEL BEING FED |
| FROM PANEL "A", HOWEVER PANEL "A" DOES |
| NOT LIST THIS PANEL, OCP ETC ON ITS |
| PANEL SCHEDULE. WHERE IS THIS PANEL FED |
| FROM? |
| FBC 106.1.2 ADMIN SECT., 215.5 , |
| 240.4,310.16 ETC. |
| |
| 2) NOTE: PLEASE CORRELATE AIC RATINGS AS |
| RISER SHOWS 22K FOR THE MCB AND PANEL |
| "A" SHOWS 10K? IF THE MAINS ARE 22K AND |
| THE BRANCH BREAKERS ARE SIZED AT SERIES |
| RATINGS, THEN PLEASE INDICATE THE 10K |
| FOR BRANCH BRKRS ONLY. IF IT SOMETHING |
| DIFFERENT, THEN PLEASE ADJUST. |
| 110.9, 106.1.2FBC |
| |
| 3) NOTE: PLEASE SEE RISER IS SHOWING |
| "EQUIPMENT GROUNDING CONDUCTORS " FROM |
| METER TO MAIN. PLEASE SEE 250.6, |
| 250.24B, AS THE EGC IS ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| |
| 4)NOTE: PLEASE SEE RISER SHOWS 100A SUB |
| PANEL BEING FED WITH 3-3/0'S?? AND #6 |
| EQUIPMENT GROUNDING CONDUCTOR?? PLEASE |
| KNOW, IT IS OK TO USE THESE OVERSIZED |
| CONDUCTORS, HOWEVER RISER SHOWS THEM IN |
| A "1/2" CONDUIT?? AND 3/0'S WILL NOT FIT |
| INTO THE 100A BRKR. PLEASE VERIFY AND |
| SEE 310.16/310.15B6 FOR SIZING. PLEASE |
| SEE CHAPTER 9 TABLES FOR CORRECT SIZING |
| OF CONDUIT FOR CONDUIT FILL. |
| 215.5. |
| |
| 5) NOTE: PLEASE INDICATE METER CAN SIZE |
| AS PREVIOUS PLANS CALLED FOR 200A |
| SERVICE. |
| 106.1.2 |
| |
| 6) NOTE: PLEASE CORRELATE ALL A/C |
| MECHANICAL LOADS, OVER CURRENT |
| PROTECTION AND WIRE SIZES. PLEASE SEE |
| OCP IS NOW MISSING FOR SOME AHU'S HEAT? |
| PLEASE SEE 424.3B FOR MIN SIZING. PLEASE |
| SEE TWO AHU'S ARE NOW SHOWING 5KW HEAT |
| YET, STILL IDNCATE 60A OCP ON LOAD |
| CALCULATIONS AND #6 WIRE. ONCE AGAIN, |
| PLEASE VERIFY THIS AS 5KW UNITS ARE NOW |
| BEING SHOWN AND 60A OCP IS WAY TOO HIGH. |
| PLEASE ALSO KNOW, #6 WIRE WILL NOT FIT |
| IN THE CORRECT SIZE BRKR THEY NEED TO |
| BE. |
| PLEASE ALSO SEE CU'S AS THESE ARE ALSO |
| SHWOING 60A OCP. UPON REVIWING THE |
| MECHANICAL EQUIPMENT SCHEDULE UNITS #2 |
| AND #3 ARE 2.5 AND 3.0 TON UNITS. PLEASE |
| CONSULT YOUR MECHANICAL PERSON AS THE |
| OCP IS WAY TOO HIGH. PLEASE ALSO ADJUST |
| THE CONDUCTOR SIZE CORRECLTY AS THE #6'S |
| WILL ALSO NOT FIT IN THE OCP NEEDED |
| ONCE THESE ARE ADJUSTED. |
| 240, 440, 430, 240.4, 310.16,ETC ETC |
| 106.1.2 FBC. |
| |
| 7) NOTE: PLEASE SEE LOAD FOR ELEVATOR ON |
| PANEL SCHEDULE DOES NOT CORRELATE WITH |
| THE LOAD CALCULATIONS.PLEASE SEE A LOAD |
| OF 3300 VA IS BEING SHOWN ON BOTH "A" |
| AND "B" PHASE WHICH WOULD BE A TOTAL |
| LOAD ON LOAD CALCS OF 6600VA. PLEASE |
| VERIFY WHAT THE LOADS ACTUALLY ARE. |
| IF LOAD IS INDEED 6600, PLEASE ADJUST |
| THE OCP AND CONDUCTOR SIZES ALONG WITH |
| REVISING THE LOAD CALCULATIONS. |
| 240.4,310.16,220 ETC. |
| |
| 8) NOTE: PLEASE SEE SMALL APPLIANCE |
| CIRCUITS ARE STILL BEING SHOWN AT |
| 2400VA. PLEASE SEE 210.11C1,220.16 AS SM |
| APPL CIRCUITS ARE 1500VA. PLEASE SEE |
| THAT 2400VA WAY EXCEEDS THE RATING OF A |
| 20A CIRCUIT. (1920VA MAX). |
| |
| 9) NOTE: PLEASE SEE LOADS SHOWN FOR |
| ELEVATOR CAR LTS AND RECEPTS WHICH SEEM |
| TO INDICATE DEDICATED LOAD OF 1080VA YET |
| THIS LOAD OS NOT ON LOAD CALCULATIONS? |
| PLEASE ALSO SEE AN ADDITIONAL LOAD OF |
| 1080VA IS SHOWN FOR ELEV CAR YET THIS IS |
| ALSO NOT SHOWN IN LOAD CALCULATIONS? |
| 220. |
| |
| 10 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 11) NOTE: PLEASE LIST ALL CIRCUITING ON |
| PANEL SCHEDULE(S) FOR SPECIFIC AREAS AND |
| PLEASE LIST ALL THE REQUIRED ARC FAULT |
| PROTECTED CIRCUITS AS REQUIRED PER |
| 210.12B,. 408.4 |
| IE; MASTERBEDRM LTS, KITCHEN LTS, |
| LIVING RM RECEPTS ETC. |
| IT IS KNOWN TO THIS OFFICE THAT THE |
| BRNACH CIRCUITING WILL MOST LIKELY |
| CHANGE SURING CONSTRUCTION , HOWEVER THE |
| MIN CIRCUITS SHALL BE ON PANEL SCHEDULES |
| AT THIS TIME. |
| |
| 12) NOTE: PLEASE SEE AN ESTIMATE LOAD OF |
| 900VA IS BEING SHOWN FOR ALL THE GEN LT |
| AND RECEPT CIRCUITS. WHERE IS THIS 900VA |
| COMING FROM. PLEASE SEE TOTAL GEN LT |
| DEMAND IS 15,000+ VA AND DOES NOT |
| CORRELATE WITH THIS. |
| PLEASE SEE NEC 220,215.5 ETC. |
| |
| 13) NOTE: PLEASE SEE THAT SMOKE |
| DETECTORS ARE REQUIRED WITHIN 12" OF THE |
| HIGHEST POINT OF ANY FLAT CEILINGS AND |
| SLOPED CEILING WITHIN 3' OF PEAK. PLEASE |
| SEE THAT IF THE TRAY CEILINGS AS SHOWN |
| ARE 12" OR MORE UP FROM OTHER |
| SURROUNDING CEILINGS AREAS, THEN THE |
| SD'S ARE REQUIRED TO BE MOVED. PLEASE |
| SEE SD'S LOCATED WITHIN 20' OF COOKING |
| APPLIANCES SHALL MEET THE EXCEPTIONS AS |
| BEING PHOTO-ELECTRIC EYE TYPE/RESETTING |
| TYPE AS REQUIRED. |
| PLEASE SEE NFPA-72 2002 11.8.3 FOR THESE |
| INSTALLATION REQUIREMENTS. |
| |
| 14) NOTE: PLEASE SEE 680.71 AS NO GFI |
| PROTECTION IS NOTED FOR WHIRLPOOL TUB. |
| PLEASE ALSO SEE THAT NO ELECTRICAL FOR |
| THIS SAME TUB IS BEING SHOWN ON PLANS?? |
| PLEASE CORRELATE. |
| 106.1.2 |
| |
| 15) NOTE: PLEASE SEE THAT THE PLANS |
| SHALL STATE THE CURRENT CODES IN EFFECT |
| FOR THE FOLLOWING. PLEASE LIST THE |
| FOLLOWING AT A MINIMUM WHICH ARE |
| RELEVANT TO THE ELECTRICAL PLANS. |
| 2002 NFPA-70( NEC), 2002 NFPA-72, 2003 |
| NFPA-101. |
| |
| 16) NOTE: PLEASE SEEMISSING EGRESS |
| LIGHTING CONTROLS WHEN EXITING TO |
| OUTSIDE FROM THE FOLLOWING AREAS. MEDIA |
| RM, LIVING RM, NOOK AND FAMILY RM. |
| PLEASE KNOW, LIGHTING MAY BE CONTROLLED |
| BY MULTIPLE LOCATIONS BY 3-/4-WAYS.(ONLY |
| A SUGGESTIONS) MUST HAVE MIN CONTROL FOR |
| SOME SORT OF LIGHTING FIXTURE. |
| NFPA-70 210.70, NFPA-101 7.8 |
| |
| 17) NOTE: PLEASE SEE 210.52B1, 210.11C1, |
| 220.16 AS DINING SHALL BE ON ONE OR MORE |
| OF THE REQUIRED SMALL APPLIANCE |
| CIRCUITS. PLEASE LIST AND SEE MIN VA |
| (1500VA) REQUIRED. |
| |
| 18) NOTE: PLEASE SEE PANEL SCHEDULE |
| SEEMS TO MENTIONS THREE CIRCUITS FOR |
| "GFI"?? HOWEVER THIS IS UNCLEAR WHAT |
| THESE ARE FOR. PLEASE LIST. |
| 408.4 |
| |
| 19) NOTE: PLEASE SEE MISSING THE |
| REQUIRED DEDICATED BATH(S) CIRCUIT(S) |
| PER 210.52D,210.11C3. MUST BE #12 AND |
| 20A. (IS CIRCUITS FROM NOTE #18 THESE??) |
| IF SO, PLEASE LABEL. |
| |
| 20) NOTE: PLEASE SEE PLANS SEEM TO |
| INDICATE SOME SORT OF "HEATER" FOR |
| FUTURE POOL EQUIPMENT?? PLEASE BE SURE |
| TO INDICATE IF GAS (FUTURE) OR |
| ELECTRIC(FUTURE). PLEASE KNOW HOWEVER, |
| IF THIS IS GOING TO BE AN ELECTRICAL |
| HEAT PUMP, THEN PLEASE KNOW THE LOAD |
| NEEDS TO BE FIGURED INTO THE SERVICE AT |
| THIS TIME. |
| PLEASE ADJUST OF ELECTRIC HEAT PUMP. |
| PLEASE ALSO KNOW, ALL CONTINOUS LOADS |
| ARE SHOWN AT 125%. (HEAT PUMP AND POOL |
| PUMP) IF THE LOAD IS ALREADY SHOWN AT |
| 125%, PLEASE NOTE. |
| 220,680.9,215.3,230.42 |
| |
| 21) NOTE: PLEASE SEE LOAD CALCULATIONS |
| SHOW PANELS AS 40CIR AND PANELS ARE |
| 42CIR. (MISPRINT/CORRELATE). |
| 106.1.2 |
| |
| 22) NOTE: PLEASE KNOW PLANS HAVE BEEN |
| SUBMITTED FIVE TIMES FOR REVIEW FOR THIS |
| SINGLE FAMILY RESIDENCE. |
| PLEASE KNOW ALL FIVE SETS OF ELECTRICAL |
| PLANS ARE BEING RETAINED. PLEASE ALSO |
| KNOW PLANS MAY BE TURNED OVER TO THE |
| FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| FOR PEIR REVIEWFOR REPEATED COMMENTS FOR |
| NON-COMPLIANCE. |
| PLEASE ALSO SEE COPY OF FS 553.80(2)(B) |
| WITH RESPECT TO DESIGN PROFESSIONALS AND |
| REPEAT COMMENTS FOR CODE COMPLIANCE. |
| PLEASE KNOW THAT IF ANY OF THE SAME CODE |
| COMPLIANT COMMENTS ARE STILL NOT |
| ADDRESSED ON THE NEXT RESUBMITTAL, THIS |
| OFFICE WILL HAVE NO CHOICE TO ASSESS A |
| 4X FEE FOR THE PLAN REVIEW PORTION OF |
| THE PERMIT FEE. |
| PLEASE SEE THIS FINE WILL BE $10,860.00 |
| WHICH IS REQUIRED UNDER FLORIDA STATUES |
| TO BE PAID BY THE DESIGN PROFESSIONAL(S) |
| OF RECORD. THIS FINE IS "NOT" THE |
| RESPONSIBILTY OF THE OWNER OR |
| CONTRACTOR. |
| PLEASE KNOW THIS OFFICE IS GIVING NOTICE |
| THAT A MEETING IS REQUIRED AND SHALL BE |
| HELDWITH THEATTENDANCE OF THE |
| FOLLOWING PERSONS AT A MINIMUM: GARRISON |
| DESIGN GROUP, MR. LUIS LOPEZ (ENGINEER |
| OF RECORD) AND GENERAL CONTRACTOR. |
| |
| 23) NOTE: PLEASE KNOW, UPON REVIEW OF |
| THE SUBMITTED PACKAGE THE ORIGINAL |
| PERMIT APPLICATION COULD NOT BE READILY |
| FOUND. PLEASE BE SURE THIS APPLICATION |
| IS LOCATED AND SUBMITTED WHEN |
| RESUBMITTING PLANS. |
| PLEASE ALSO KNOW THAT ANY NOTICE OF |
| COMMENCEMENTS NOT RECORDED WITHIN 90 |
| DAYS OF ISSUANCE OF THE PERMMIT WILL |
| REQUIRE THE NOC TO BE RE-RECORDED PER FS |
| 713.13(2). PER FS AS NOTED, IF WORK HAS |
| NOT COMMENCED WITHIN 90 DAYS OF |
| RECORDING SUCH NOC, THE NOC SHALL BECOME |
| VOID. |
| IF THERE ARE ANY QUESTIONS ON THIS, |
| PLEASE CALL. |
| |
| ** PLEASE BE SURE TO CAREFULLY STAPLE |
| ALL NEW SETS , AS THE SETS WERE ATTACHED |
| THROUGH THE PANEL SCHEDULES CAUSING |
| THESE TO BE TORN FOR REVIEW. PLEASE ALSO |
| TO SUBMIT TWO COMPLETE AND CLEAN SETS |
| FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |