Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop E
Sequence Number 6
Notes
Date Text
2006-07-25 00:00:00*********** UNSAT 5TH REVIEW *********
  
 ** PLEAS SEE THIS IS THE 5TH REVIEW.
 PLEASE SEE SOME COMMENTS BELOW ARE STILL
 IN NEED OF BEING ADDRESSED FROM PREVIOUS
 REVIEWS AND PLEASE SEE SOME NEW
 COMMENTS.
  
  
 1) NOTE: PLEASE SEE SERVICE RISER IS
 STILL VERY UNCLEAR AS THE 100A MCB SUB
 PANEL IS NOT FED FROM ANYWHERE? PLEASE
 SEE RISER SHOWS THIS PANEL BEING FED
 FROM PANEL "A", HOWEVER PANEL "A" DOES
 NOT LIST THIS PANEL, OCP ETC ON ITS
 PANEL SCHEDULE. WHERE IS THIS PANEL FED
 FROM?
 FBC 106.1.2 ADMIN SECT., 215.5 ,
 240.4,310.16 ETC.
  
 2) NOTE: PLEASE CORRELATE AIC RATINGS AS
 RISER SHOWS 22K FOR THE MCB AND PANEL
 "A" SHOWS 10K? IF THE MAINS ARE 22K AND
 THE BRANCH BREAKERS ARE SIZED AT SERIES
 RATINGS, THEN PLEASE INDICATE THE 10K
 FOR BRANCH BRKRS ONLY. IF IT SOMETHING
 DIFFERENT, THEN PLEASE ADJUST.
 110.9, 106.1.2FBC
  
 3) NOTE: PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS " FROM
 METER TO MAIN. PLEASE SEE 250.6,
 250.24B, AS THE EGC IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE RISER SHOWS 100A SUB
 PANEL BEING FED WITH 3-3/0'S?? AND #6
 EQUIPMENT GROUNDING CONDUCTOR?? PLEASE
 KNOW, IT IS OK TO USE THESE OVERSIZED
 CONDUCTORS, HOWEVER RISER SHOWS THEM IN
 A "1/2" CONDUIT?? AND 3/0'S WILL NOT FIT
 INTO THE 100A BRKR. PLEASE VERIFY AND
 SEE 310.16/310.15B6 FOR SIZING. PLEASE
 SEE CHAPTER 9 TABLES FOR CORRECT SIZING
 OF CONDUIT FOR CONDUIT FILL.
 215.5.
  
 5) NOTE: PLEASE INDICATE METER CAN SIZE
 AS PREVIOUS PLANS CALLED FOR 200A
 SERVICE.
 106.1.2
  
 6) NOTE: PLEASE CORRELATE ALL A/C
 MECHANICAL LOADS, OVER CURRENT
 PROTECTION AND WIRE SIZES. PLEASE SEE
 OCP IS NOW MISSING FOR SOME AHU'S HEAT?
 PLEASE SEE 424.3B FOR MIN SIZING. PLEASE
 SEE TWO AHU'S ARE NOW SHOWING 5KW HEAT
 YET, STILL IDNCATE 60A OCP ON LOAD
 CALCULATIONS AND #6 WIRE. ONCE AGAIN,
 PLEASE VERIFY THIS AS 5KW UNITS ARE NOW
 BEING SHOWN AND 60A OCP IS WAY TOO HIGH.
 PLEASE ALSO KNOW, #6 WIRE WILL NOT FIT
 IN THE CORRECT SIZE BRKR THEY NEED TO
 BE.
 PLEASE ALSO SEE CU'S AS THESE ARE ALSO
 SHWOING 60A OCP. UPON REVIWING THE
 MECHANICAL EQUIPMENT SCHEDULE UNITS #2
 AND #3 ARE 2.5 AND 3.0 TON UNITS. PLEASE
 CONSULT YOUR MECHANICAL PERSON AS THE
 OCP IS WAY TOO HIGH. PLEASE ALSO ADJUST
 THE CONDUCTOR SIZE CORRECLTY AS THE #6'S
 WILL ALSO NOT FIT IN THE OCP NEEDED
 ONCE THESE ARE ADJUSTED.
 240, 440, 430, 240.4, 310.16,ETC ETC
 106.1.2 FBC.
  
 7) NOTE: PLEASE SEE LOAD FOR ELEVATOR ON
 PANEL SCHEDULE DOES NOT CORRELATE WITH
 THE LOAD CALCULATIONS.PLEASE SEE A LOAD
 OF 3300 VA IS BEING SHOWN ON BOTH "A"
 AND "B" PHASE WHICH WOULD BE A TOTAL
 LOAD ON LOAD CALCS OF 6600VA. PLEASE
 VERIFY WHAT THE LOADS ACTUALLY ARE.
 IF LOAD IS INDEED 6600, PLEASE ADJUST
 THE OCP AND CONDUCTOR SIZES ALONG WITH
 REVISING THE LOAD CALCULATIONS.
 240.4,310.16,220 ETC.
  
 8) NOTE: PLEASE SEE SMALL APPLIANCE
 CIRCUITS ARE STILL BEING SHOWN AT
 2400VA. PLEASE SEE 210.11C1,220.16 AS SM
 APPL CIRCUITS ARE 1500VA. PLEASE SEE
 THAT 2400VA WAY EXCEEDS THE RATING OF A
 20A CIRCUIT. (1920VA MAX).
  
 9) NOTE: PLEASE SEE LOADS SHOWN FOR
 ELEVATOR CAR LTS AND RECEPTS WHICH SEEM
 TO INDICATE DEDICATED LOAD OF 1080VA YET
 THIS LOAD OS NOT ON LOAD CALCULATIONS?
 PLEASE ALSO SEE AN ADDITIONAL LOAD OF
 1080VA IS SHOWN FOR ELEV CAR YET THIS IS
 ALSO NOT SHOWN IN LOAD CALCULATIONS?
 220.
  
 10 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 11) NOTE: PLEASE LIST ALL CIRCUITING ON
 PANEL SCHEDULE(S) FOR SPECIFIC AREAS AND
 PLEASE LIST ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS AS REQUIRED PER
 210.12B,. 408.4
 IE; MASTERBEDRM LTS, KITCHEN LTS,
 LIVING RM RECEPTS ETC.
 IT IS KNOWN TO THIS OFFICE THAT THE
 BRNACH CIRCUITING WILL MOST LIKELY
 CHANGE SURING CONSTRUCTION , HOWEVER THE
 MIN CIRCUITS SHALL BE ON PANEL SCHEDULES
 AT THIS TIME.
  
 12) NOTE: PLEASE SEE AN ESTIMATE LOAD OF
 900VA IS BEING SHOWN FOR ALL THE GEN LT
 AND RECEPT CIRCUITS. WHERE IS THIS 900VA
 COMING FROM. PLEASE SEE TOTAL GEN LT
 DEMAND IS 15,000+ VA AND DOES NOT
 CORRELATE WITH THIS.
 PLEASE SEE NEC 220,215.5 ETC.
  
 13) NOTE: PLEASE SEE THAT SMOKE
 DETECTORS ARE REQUIRED WITHIN 12" OF THE
 HIGHEST POINT OF ANY FLAT CEILINGS AND
 SLOPED CEILING WITHIN 3' OF PEAK. PLEASE
 SEE THAT IF THE TRAY CEILINGS AS SHOWN
 ARE 12" OR MORE UP FROM OTHER
 SURROUNDING CEILINGS AREAS, THEN THE
 SD'S ARE REQUIRED TO BE MOVED. PLEASE
 SEE SD'S LOCATED WITHIN 20' OF COOKING
 APPLIANCES SHALL MEET THE EXCEPTIONS AS
 BEING PHOTO-ELECTRIC EYE TYPE/RESETTING
 TYPE AS REQUIRED.
 PLEASE SEE NFPA-72 2002 11.8.3 FOR THESE
 INSTALLATION REQUIREMENTS.
  
 14) NOTE: PLEASE SEE 680.71 AS NO GFI
 PROTECTION IS NOTED FOR WHIRLPOOL TUB.
 PLEASE ALSO SEE THAT NO ELECTRICAL FOR
 THIS SAME TUB IS BEING SHOWN ON PLANS??
 PLEASE CORRELATE.
 106.1.2
  
 15) NOTE: PLEASE SEE THAT THE PLANS
 SHALL STATE THE CURRENT CODES IN EFFECT
 FOR THE FOLLOWING. PLEASE LIST THE
 FOLLOWING AT A MINIMUM WHICH ARE
 RELEVANT TO THE ELECTRICAL PLANS.
 2002 NFPA-70( NEC), 2002 NFPA-72, 2003
 NFPA-101.
  
 16) NOTE: PLEASE SEEMISSING EGRESS
 LIGHTING CONTROLS WHEN EXITING TO
 OUTSIDE FROM THE FOLLOWING AREAS. MEDIA
 RM, LIVING RM, NOOK AND FAMILY RM.
 PLEASE KNOW, LIGHTING MAY BE CONTROLLED
 BY MULTIPLE LOCATIONS BY 3-/4-WAYS.(ONLY
 A SUGGESTIONS) MUST HAVE MIN CONTROL FOR
 SOME SORT OF LIGHTING FIXTURE.
 NFPA-70 210.70, NFPA-101 7.8
  
 17) NOTE: PLEASE SEE 210.52B1, 210.11C1,
 220.16 AS DINING SHALL BE ON ONE OR MORE
 OF THE REQUIRED SMALL APPLIANCE
 CIRCUITS. PLEASE LIST AND SEE MIN VA
 (1500VA) REQUIRED.
  
 18) NOTE: PLEASE SEE PANEL SCHEDULE
 SEEMS TO MENTIONS THREE CIRCUITS FOR
 "GFI"?? HOWEVER THIS IS UNCLEAR WHAT
 THESE ARE FOR. PLEASE LIST.
 408.4
  
 19) NOTE: PLEASE SEE MISSING THE
 REQUIRED DEDICATED BATH(S) CIRCUIT(S)
 PER 210.52D,210.11C3. MUST BE #12 AND
 20A. (IS CIRCUITS FROM NOTE #18 THESE??)
 IF SO, PLEASE LABEL.
  
 20) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE SOME SORT OF "HEATER" FOR
 FUTURE POOL EQUIPMENT?? PLEASE BE SURE
 TO INDICATE IF GAS (FUTURE) OR
 ELECTRIC(FUTURE). PLEASE KNOW HOWEVER,
 IF THIS IS GOING TO BE AN ELECTRICAL
 HEAT PUMP, THEN PLEASE KNOW THE LOAD
 NEEDS TO BE FIGURED INTO THE SERVICE AT
 THIS TIME.
 PLEASE ADJUST OF ELECTRIC HEAT PUMP.
 PLEASE ALSO KNOW, ALL CONTINOUS LOADS
 ARE SHOWN AT 125%. (HEAT PUMP AND POOL
 PUMP) IF THE LOAD IS ALREADY SHOWN AT
 125%, PLEASE NOTE.
 220,680.9,215.3,230.42
  
 21) NOTE: PLEASE SEE LOAD CALCULATIONS
 SHOW PANELS AS 40CIR AND PANELS ARE
 42CIR. (MISPRINT/CORRELATE).
 106.1.2
  
 22) NOTE: PLEASE KNOW PLANS HAVE BEEN
 SUBMITTED FIVE TIMES FOR REVIEW FOR THIS
 SINGLE FAMILY RESIDENCE.
 PLEASE KNOW ALL FIVE SETS OF ELECTRICAL
 PLANS ARE BEING RETAINED. PLEASE ALSO
 KNOW PLANS MAY BE TURNED OVER TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 FOR PEIR REVIEWFOR REPEATED COMMENTS FOR
 NON-COMPLIANCE.
 PLEASE ALSO SEE COPY OF FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THAT IF ANY OF THE SAME CODE
 COMPLIANT COMMENTS ARE STILL NOT
 ADDRESSED ON THE NEXT RESUBMITTAL, THIS
 OFFICE WILL HAVE NO CHOICE TO ASSESS A
 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE.
 PLEASE SEE THIS FINE WILL BE $10,860.00
 WHICH IS REQUIRED UNDER FLORIDA STATUES
 TO BE PAID BY THE DESIGN PROFESSIONAL(S)
 OF RECORD. THIS FINE IS "NOT" THE
 RESPONSIBILTY OF THE OWNER OR
 CONTRACTOR.
 PLEASE KNOW THIS OFFICE IS GIVING NOTICE
 THAT A MEETING IS REQUIRED AND SHALL BE
 HELDWITH THEATTENDANCE OF THE
 FOLLOWING PERSONS AT A MINIMUM: GARRISON
 DESIGN GROUP, MR. LUIS LOPEZ (ENGINEER
 OF RECORD) AND GENERAL CONTRACTOR.
  
 23) NOTE: PLEASE KNOW, UPON REVIEW OF
 THE SUBMITTED PACKAGE THE ORIGINAL
 PERMIT APPLICATION COULD NOT BE READILY
 FOUND. PLEASE BE SURE THIS APPLICATION
 IS LOCATED AND SUBMITTED WHEN
 RESUBMITTING PLANS.
 PLEASE ALSO KNOW THAT ANY NOTICE OF
 COMMENCEMENTS NOT RECORDED WITHIN 90
 DAYS OF ISSUANCE OF THE PERMMIT WILL
 REQUIRE THE NOC TO BE RE-RECORDED PER FS
 713.13(2). PER FS AS NOTED, IF WORK HAS
 NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING SUCH NOC, THE NOC SHALL BECOME
 VOID.
 IF THERE ARE ANY QUESTIONS ON THIS,
 PLEASE CALL.
  
 ** PLEASE BE SURE TO CAREFULLY STAPLE
 ALL NEW SETS , AS THE SETS WERE ATTACHED
 THROUGH THE PANEL SCHEDULES CAUSING
 THESE TO BE TORN FOR REVIEW. PLEASE ALSO
 TO SUBMIT TWO COMPLETE AND CLEAN SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  