Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop M
Sequence Number 4
Notes
Date Text
2006-07-24 00:00:00*** DENIED ***
 1) AHU #1 12" TRUNK LINE IS TO SMALL FOR
 907 CFM'S SEE MANUAL 'J' CALCULATIONS
 MAX. VELOCITY 900 FPM, THEREFORE 14"
 WOULD BE REQUIRED. AND THE 10" TRUNK
 LINE WOULD NEED TO BE 12", PLESE
 CORRECT.
  
 2) A/C SYSTEM #3 IS LISTED AS A 3.5 TON
 BUT IS A 2.5 TON PLEASE CORRECT.
  
 3) SEE 4" DUCT TO MEDIA ROOM AND 8" DUCT
 TO WALKIN CLOSET, PLEASE CORRECT.
  
 4) IS AHU #1 GOING IN THE PANTRY OR IN
 THE ALOSET WITH THE WATER HEATER, SEE
 ELECTRICAL PLANS AND MECHANICAL PLANS,
 PLEASE CORRECT.
  
 5) SEE 7" DUCT TO HIS CLOSET, PLANS ALSO
 SHOW (2)6X6 1W 30 CFM, PLEASE CORRECT.
  
 6) AHU IN MASTER SUITE IS MARKED AS AHU
 #2 BUT IS AHU #3, PLEASE CORRECT.
  
 7) AHU OVER UTILITY ROOM IS MARKED AS
 AHU #3, BUT IS AHU #2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.