Plan Review Notes For Permit 06010171 |
Permit Number |
06010171 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-07-24 00:00:00 | *** DENIED *** | | 1) AHU #1 12" TRUNK LINE IS TO SMALL FOR | | 907 CFM'S SEE MANUAL 'J' CALCULATIONS | | MAX. VELOCITY 900 FPM, THEREFORE 14" | | WOULD BE REQUIRED. AND THE 10" TRUNK | | LINE WOULD NEED TO BE 12", PLESE | | CORRECT. | | | | 2) A/C SYSTEM #3 IS LISTED AS A 3.5 TON | | BUT IS A 2.5 TON PLEASE CORRECT. | | | | 3) SEE 4" DUCT TO MEDIA ROOM AND 8" DUCT | | TO WALKIN CLOSET, PLEASE CORRECT. | | | | 4) IS AHU #1 GOING IN THE PANTRY OR IN | | THE ALOSET WITH THE WATER HEATER, SEE | | ELECTRICAL PLANS AND MECHANICAL PLANS, | | PLEASE CORRECT. | | | | 5) SEE 7" DUCT TO HIS CLOSET, PLANS ALSO | | SHOW (2)6X6 1W 30 CFM, PLEASE CORRECT. | | | | 6) AHU IN MASTER SUITE IS MARKED AS AHU | | #2 BUT IS AHU #3, PLEASE CORRECT. | | | | 7) AHU OVER UTILITY ROOM IS MARKED AS | | AHU #3, BUT IS AHU #2, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|