Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop E
Sequence Number 4
Notes
Date Text
2006-07-05 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATION @218.5 AMPS
 EXCEEDS THE SERVICE SIZE OF 200 AMPS.
 230.31 SIZE AND RATING.
 (A) GENERAL. SERVICE-LATERAL CONDUCTORS
 SHALL HAVE SUFFICIENT AMPACITY TO CARRY
 THE CURRENT FOR THE LOAD AS COMPUTED IN
 ACCORDANCE WITH ARTICLE 220 AND SHALL
 HAVE ADEQUATE MECHANICAL STRENGTH.
 SUGGEST LARGER SERVICE.
  
 2} THE 3/0 FEEDERS FOR 250 AMPS DOES NOT
 COMPLY WITH 310.15(B)(6).
  
 3} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE SIZED PER 250.66, MINIMUM OF A
 #2 COPPER FOR 250 AMP OCP.
  
 4} THE FEEDER FOR PANEL "B" IS NOT
 LISTED IN PANEL "A".
  
 5} THE SMALL APPLIANCE CIRCUITS @ 2400
 VA ARE TOO LARGE FOR A 20 AMP CIRCUIT
 SEE 220.16 FOR LOAD CALCULATION
 REQUIREMENTS, SMALL APPLIANCE.
  
 6} THE LAUNDRY CIRCUIT CALCULATION
 REQUIRED BY 220.16(B), IS NOT IN THE
 LOAD CALCULATION.
  
 7} THE A/C CALCULATIONS ON THE
 ELECTRICAL PLAN DOES NOT CORRESPOND TO
 THE MECHANICAL PLAN. PLEASE CORRELATE
 SAME.
  
 8} PLEASE SEE THE GFI LOCATED IN THE
 SINK IN THE CABANA BATH.
  
 9} BEDROOMS 1 AND 3 NEED A RECEPTACLE
 ADDED PER 210.52(A)(1).
  
 10} PLEASE INSERT ALL NEW PAGES INTO ONE
 COMPLETE SET OF PLANS WHEN RESUBMITTING.
 ALSO DO NOT RESUBMIT SHEETS FROM OLD
 REVIEWS OTHER THAN THE PREVIOUS REVIEW,
 REMOVE ALL OTHERS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW