2006-07-05 00:00:00 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE LOAD CALCULATION @218.5 AMPS |
| EXCEEDS THE SERVICE SIZE OF 200 AMPS. |
| 230.31 SIZE AND RATING. |
| (A) GENERAL. SERVICE-LATERAL CONDUCTORS |
| SHALL HAVE SUFFICIENT AMPACITY TO CARRY |
| THE CURRENT FOR THE LOAD AS COMPUTED IN |
| ACCORDANCE WITH ARTICLE 220 AND SHALL |
| HAVE ADEQUATE MECHANICAL STRENGTH. |
| SUGGEST LARGER SERVICE. |
| |
| 2} THE 3/0 FEEDERS FOR 250 AMPS DOES NOT |
| COMPLY WITH 310.15(B)(6). |
| |
| 3} THE GROUNDING ELECTRODE CONDUCTOR |
| MUST BE SIZED PER 250.66, MINIMUM OF A |
| #2 COPPER FOR 250 AMP OCP. |
| |
| 4} THE FEEDER FOR PANEL "B" IS NOT |
| LISTED IN PANEL "A". |
| |
| 5} THE SMALL APPLIANCE CIRCUITS @ 2400 |
| VA ARE TOO LARGE FOR A 20 AMP CIRCUIT |
| SEE 220.16 FOR LOAD CALCULATION |
| REQUIREMENTS, SMALL APPLIANCE. |
| |
| 6} THE LAUNDRY CIRCUIT CALCULATION |
| REQUIRED BY 220.16(B), IS NOT IN THE |
| LOAD CALCULATION. |
| |
| 7} THE A/C CALCULATIONS ON THE |
| ELECTRICAL PLAN DOES NOT CORRESPOND TO |
| THE MECHANICAL PLAN. PLEASE CORRELATE |
| SAME. |
| |
| 8} PLEASE SEE THE GFI LOCATED IN THE |
| SINK IN THE CABANA BATH. |
| |
| 9} BEDROOMS 1 AND 3 NEED A RECEPTACLE |
| ADDED PER 210.52(A)(1). |
| |
| 10} PLEASE INSERT ALL NEW PAGES INTO ONE |
| COMPLETE SET OF PLANS WHEN RESUBMITTING. |
| ALSO DO NOT RESUBMIT SHEETS FROM OLD |
| REVIEWS OTHER THAN THE PREVIOUS REVIEW, |
| REMOVE ALL OTHERS. |
| |