Plan Review Notes
Plan Review Notes For Permit 06010171
Permit Number 06010171
Review Stop M
Sequence Number 3
Notes
Date Text
2006-07-05 00:00:00*** DENIED ***
 1) PLEASE SEE MANUAL J CALCULATIONS PAGE
 7 AND CORRECT THE EQUIPMENT LISTING FOR
 A/C SYSTEM #3 (MASTER SUITE).
  
 2) PLEASE CORRECT THE EQUIPMENT LISTING
 AS TWO A/C SYSTEMS ARE LISTED AS #2.
  
 3) PLEASE SHOW ON MECHANICAL PLANS AS
 YOU HAVE ON THE ELECTRICAL PLANS, THAT
 THE GAS CLOTHES DRYER AND GAS WATER
 HEATER ARE DIRECT VENTED.
  
 4) PLEASE SEE HIGH-LITED DUCTS ON
 MECHANICAL PLANS AS SOME ARE NOT SIZED
 AND SOME ARE RUNNING INTO OTHER DUCTS
 WITH NO MIXING BOXES AND NO SIZE
 CHANGES.
  
 5) PLEASE SEE ELECTRICAL REVIEW NOTES #7
 AND #10, AND CORRECT.
  
 6) PLEASE REMOVE ALL OLD PLANS AND
 SUBMIT TWO COMPLETE SETS OF PLANS, THE
 SETS SHOULD INCLUDE ANY APPROVED STAMPED
 PAGES FROM PAST REVIEWS (PLUMBING &
 ZONING).
  
 7) PLEASE BE ADVISED THAT NOTE #6 HAS
 BEEN REQUESTED NUMEROUS TIMES BY OTHER
 DEPARTMENTS, AND SEE ATTACHED ADVISORY
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.