Plan Review Notes For Permit 06010171 |
Permit Number |
06010171 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-06-12 00:00:00 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE LOAD CALCULATION @254 AMPS | | EXCEEDS THE SERVICE SIZE OF 200 AMPS. | | 230.31 SIZE AND RATING. | | (A) GENERAL. SERVICE-LATERAL CONDUCTORS | | SHALL HAVE SUFFICIENT AMPACITY TO CARRY | | THE CURRENT FOR THE LOAD AS COMPUTED IN | | ACCORDANCE WITH ARTICLE 220 AND SHALL | | HAVE ADEQUATE MECHANICAL STRENGTH.. | | | | 2} PROVIDE PANEL SCHEDULES FOR PANELS | | "A" AND "C". 408.4 NEC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | CONSTRUCTION SERVICES DEPARTMENT | | 561) 805-6718 |
|