2006-06-12 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATION @254 AMPS
 EXCEEDS THE SERVICE SIZE OF 200 AMPS.
 230.31 SIZE AND RATING.
 (A) GENERAL. SERVICE-LATERAL CONDUCTORS
 SHALL HAVE SUFFICIENT AMPACITY TO CARRY
 THE CURRENT FOR THE LOAD AS COMPUTED IN
 ACCORDANCE WITH ARTICLE 220 AND SHALL
 HAVE ADEQUATE MECHANICAL STRENGTH..
  
 2} PROVIDE PANEL SCHEDULES FOR PANELS
 "A" AND "C". 408.4 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER