Notes |
Date |
Text |
2006-04-12 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THERE IS NO CONSIDERATION FOR FUTURE | | EXPANSION REGARDING THE SERVICE SIZE OF | | 200 AMPS WITH A CORRECTED CALCULATED | | LOAD OF 209 AMPS. SEE ARTICLE 220 NEC. | | | | 2} THE RISER INDICATES A METER/MAIN | | COMBINATION SERVICE, BUT THE EQUIPMENT | | SHOWN AT LOCATION ON THE PLAN ARE STAND | | ALONE, PLEASE CLARIFY. | | | | 3} THE DISCONNECT LOCATION FOR THE | | CONDENSING UNITS DO NOT MEET 110.26 | | SPACING REQUIREMENTS. | | | | 4} SEE SOME BATHROOMS NOT COMPLY WITH | | 210.52(D). | | | | NOTES FROM PREVIOUS REVIEW: | | | | 3} THE NOTE REGARDING "RECEPTACLES ON | | ARC FAULT CIRCUITS" SHOULD READ | | "OUTLETS", SEE PRIOR COMMENT AND SEE | | 210.12. | | | | 6} THERE ARE SEVERAL ROOMS WHERE THE | | RECEPTACLE SPACING DOES NOT COMPLY WITH | | 210.52(A)(1&2). SEE REVIEWED SET OF | | PLANS FOR APPROXIMATE LOCATIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|