2006-04-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE IS NO CONSIDERATION FOR FUTURE
 EXPANSION REGARDING THE SERVICE SIZE OF
 200 AMPS WITH A CORRECTED CALCULATED
 LOAD OF 209 AMPS. SEE ARTICLE 220 NEC.
  
 2} THE RISER INDICATES A METER/MAIN
 COMBINATION SERVICE, BUT THE EQUIPMENT
 SHOWN AT LOCATION ON THE PLAN ARE STAND
 ALONE, PLEASE CLARIFY.
  
 3} THE DISCONNECT LOCATION FOR THE
 CONDENSING UNITS DO NOT MEET 110.26
 SPACING REQUIREMENTS.
  
 4} SEE SOME BATHROOMS NOT COMPLY WITH
 210.52(D).
  
 NOTES FROM PREVIOUS REVIEW:
  
 3} THE NOTE REGARDING "RECEPTACLES ON
 ARC FAULT CIRCUITS" SHOULD READ
 "OUTLETS", SEE PRIOR COMMENT AND SEE
 210.12.
  
 6} THERE ARE SEVERAL ROOMS WHERE THE
 RECEPTACLE SPACING DOES NOT COMPLY WITH
 210.52(A)(1&2). SEE REVIEWED SET OF
 PLANS FOR APPROXIMATE LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW