2006-01-10 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE A RISER DIAGRAM, SERVICE | | EQUIPMENT LOCATIONS AND PANEL SCHEDULES | | PER 215.5. | | | | 2}REGARDING THE NOTE REFERRING TO | | SMOKE DETECTORS, THEY MUST BE ON AN ARC | | FAULT BREAKER PER 210.12. | | | | 3} THE NOTE REGARDING "RECEPTACLES ON | | ARC FAULT CIRCUITS" SHOULD READ | | "OUTLETS", SEE PRIOR COMMENT AND SEE | | 210.12. | | | | 4} THERE IS NO ELEVATOR EQUIPMENT IN THE | | CALCULATIONS, BUT ONE SHOWN ON THE PLAN. | | SEE ARTICLE 620. | | | | 5} PLEASE SHOW THE LOCATION OF ALL | | EQUIPMENT ON THE PLAN. POOL PUMPS, | | CONDENSING UNITS ETC. SO THAT DISCONNECT | | LOCATIONS AND SERVICE RECEPTACLE | | PLACEMENT CAN BE REVIEWED. | | | | 6} THERE ARE SEVERAL ROOMS WHERE THE | | RECEPTACLE SPACING DOES NOT COMPLY WITH | | 210.52(A)(1&2). SEE REVIEWED SET OF | | PLANS FOR APPROXIMATE LOCATIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|