2006-01-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM, SERVICE
 EQUIPMENT LOCATIONS AND PANEL SCHEDULES
 PER 215.5.
  
 2}REGARDING THE NOTE REFERRING TO
 SMOKE DETECTORS, THEY MUST BE ON AN ARC
 FAULT BREAKER PER 210.12.
  
 3} THE NOTE REGARDING "RECEPTACLES ON
 ARC FAULT CIRCUITS" SHOULD READ
 "OUTLETS", SEE PRIOR COMMENT AND SEE
 210.12.
  
 4} THERE IS NO ELEVATOR EQUIPMENT IN THE
 CALCULATIONS, BUT ONE SHOWN ON THE PLAN.
 SEE ARTICLE 620.
  
 5} PLEASE SHOW THE LOCATION OF ALL
 EQUIPMENT ON THE PLAN. POOL PUMPS,
 CONDENSING UNITS ETC. SO THAT DISCONNECT
 LOCATIONS AND SERVICE RECEPTACLE
 PLACEMENT CAN BE REVIEWED.
  
 6} THERE ARE SEVERAL ROOMS WHERE THE
 RECEPTACLE SPACING DOES NOT COMPLY WITH
 210.52(A)(1&2). SEE REVIEWED SET OF
 PLANS FOR APPROXIMATE LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  