Plan Review Notes
Plan Review Notes For Permit 06010156
Permit Number 06010156
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE PERMIT IS SUBMITTED
 FOR TIE-DOWN ONLY , HOWEVER WHERE IS THE
 PERMIT APPLICATION FOR THE INSTALLATION
 OF THESE TRAILERS?
  
 2)NOTE: PLEASE SEE THE STATE TRAILERS
 SEEM TO INDICATE CHANGES OTHER THAN THE
 WAY THESE ARE TYPICALLY WIRED FROM THE
 MANUFACTURE. PLEASE SEE PLANS ARE
 PHOTO-COPIES OF PLANS WHICH WERE STAMPED
 FROM THE STATE.
 PLEASE ALSO SEE A TITLE BLOCK ADDED FOR
 ENGINEER. PLEASE SEE THE STATE OF
 FLORIDA WEBSITE DOES NOT LIST THIS
 ENGINEER. PLEASE ALSO SEE THE PLANS
 CONTAINED A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE WHICH VIOLATES FS
 471.025
 PLEASE KNOW THIS IS THE 2ND SUCH PROJECT
 IN WHICH THE SAME SAID THINGSHAVE BEEN
 DONE AND SUBMITTED FOR PERMITTING.
 PLEASE KNOW, THE PLANS MAY BE RETAINED
 AND SUBMITTED TO THE STATE BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW.
 PLEASE CORRECT OR PROVIDE ORIGIANL
 STAMPED, UN-ALTERED STATE APPROVED
 TRAILER PLANS.
  
 3)NOTE: PLEASE PROVIDE A RISER DIAGRAM
 FOR THE HOOK-UP OF ALL FOUR TRAILERS.
 PLEASE BE SURE TO CORRELATE ALL LOADS AS
 SHOWN.
 215.5
 THE RISER DIAGRAM FOR HOOK-UP MAY BE
 DRAWN BY ELECTRICAL CONTRACTOR. IF
 INDEED THIS IS DONE FOR THIS SCOPE OF
 WORK ONLY, PLEASE HAVE THE CONTRACTOR
 PRINT NAME AND SIGN PLANS. PER FS 489,
 FBC ADMIN SECTION, 106.3.4.3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]