Date |
Text |
2006-12-20 18:46:26 | *** UNSAT 5TH REVIEW *** |
| |
| ** PLEASE SEE NOTES FROM THE FOUR PREVIOUS REVIEWS AS |
| FOLLOWS. |
| PLEASE CALL IS THERE ARE ANY QUESTIONS OR COMMENTS. |
| |
| |
| 1) NOTE:PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW |
| DATED 11/16/06. PLEASE SEE THAT THE MANUFACTURES SPECS |
| DO NOT CORRELATE WITH THE SAME INFORMATION AS PROVIDED |
| ON PLANS. PLEASE SEE THE SPECIFIC UNIT IS NOT CHECKED, |
| MARKED, HIGHLIGHTED OR NOTED FOR THE PARTICULAR UNIT. |
| PLEASE SEE THE COMMENTS BELOW. |
| PLEASE SEE SPECS FOR THE ATS WHICH ARE ONLY NOW BEING |
| SUBMITTED FOR REVIEW WOULD STILL NEED TO INDICATE BEING |
| 3R LISTED AS WELL AS RISER INDICATING THE SAME. 90.7, |
| 110.3, |
| FBC 106.1.2 |
| |
| ** PREVIOUS REVIEW NOTES BELOW FROM REVIEW#4 DATED |
| 11/16/06 ** |
| NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE SPECS WERE |
| SUBMITTED, HOWEVER AS REQUESTED IN THE PREVIOUS REVIEWS |
| PLEASE BE SURE ALL EQUIPMENT CORRELATES FOR USE AND |
| INSTALLATION ETC. |
| PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A |
| FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE |
| SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL |
| BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN |
| SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF |
| 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES |
| MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS |
| ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET |
| THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE. |
| PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE |
| ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT |
| SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED. |
| PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS. |
| PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND |
| KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS |
| THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS |
| INDICATES 42KW, AND THE NEED TO CORRELATE THE |
| MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF |
| THE UTMOST IMPORTANCE. |
| PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83" |
| LONG, 40" WIDE AND 72" IN HEIGHT. |
| PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED |
| WE ARE UNABLE TO VERIFY. |
| PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF |
| THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE |
| UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE |
| CLEARANCE IF THE UNIT IS 72" HIGH. |
| PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE |
| AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON |
| EQUIPMENT HAVE BEEN SUBMITTED. |
| PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS. |
| |
| ** PLEASE KNOW BASED ON THESE COMMENT FOR THE |
| GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY |
| NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE |
| TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST |
| ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED |
| TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL |
| WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT |
| AT THIS TIME. |
| |
| |
| ** PREVIOUS REVIEW COMMENT REVIEW #3** |
| PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT |
| SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD |
| REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES |
| WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR |
| AND ETC. |
| PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT, |
| HOWEVER PLEASE SEE PLEASE SUBMIT THE |
| MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS, |
| AND WP HOUSING. |
| PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME |
| ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK |
| SUBMITTED WHICH DO NOT APPLY AT ALL TO GEN ETC. PLEASE |
| SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM FORD |
| MOTOR CORP? |
| PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS |
| BOOKS AND SHEETS AND SOME ARE NOT THE SAME |
| EQUIPMENT??? |
| |
| ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT |
| SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE |
| THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND |
| ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND |
| STAMPING. |
| |
| FBC 106.1, 106.1.2, 110.3, 90.7 ETC. |
| |
| 2) NOTE: PLEASE SEE REVIEW NOTE #3 FROM THE PREVIOUS |
| REVIEW. |
| PLEASE SEE NOT ENERGY CALCULATIONS/LIGHTING POWER |
| DENSITIES FOR CODE COMPLIANCE WERE SUBMITTED. PLEASE |
| SEE NOTE BELOW WHICH SPEAKS OF THE "BLOCK" LOCATED ON |
| PLANS WHICH DID NOT PROVIDE THE INFORMATION AS NEEDED |
| AND REQUIRED PER 13-415.1.AB.1, 13-415.2. |
| |
| *** PREVIOUS REVIEW NOTE REVIEW, REVIEW #4DATED |
| 11/16/06** |
| NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED. THIS |
| WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL |
| REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE |
| REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED |
| WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE |
| LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE |
| THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW. |
| PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH |
| A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT |
| ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY |
| REFERENCED. |
| PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S) |
| AND SECTION. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER |
| DENSITIES, PER FBC |
| 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES |
| 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE |
| SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW |
| COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE |
| LOCATED IN PACKAGE. IN EITHER CASE, PLEASE SUBMIT. |
| |
| |
| |
| ** NEW NOTE FOR REVIEW NUMBER 5*** |
| |
| 1) NOTE: PLEASE CORRELATE PLANS AND LAYOUT OF |
| MAINS/PANELS AND DISCONNECTS ON RISER WITH THAT OF THE |
| LAYOUT SHOWN ON E-5. |
| PLEASE SEE THE MAIN DISCONNECT FOR THE SECONDARY SIDE |
| OF THE TRANSFORMER COULD NOT BE CLEARLY LOCATED. |
| |
| 2) NOTE: PLEASE SEE AS PLANS ARE NOW INDICATING THE |
| LOCATION OF ALL EQUIPMENT BEING MOVED TO THE NEW |
| LOCATION PLEASE CLARIFY THIS AS THE SUBMITTAL BOOKS FOR |
| THE NEW STRUCTURAL MEZZANINE LEVEL FROM PREVIOUS |
| SUBMITTED PLANS ARE STILL BEING SUBMITTED. PLEASE SEE |
| ANY BUILDING REVIEW COMMENTS. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2006-12-20 06:52:55 | REVIEW IN PROGRESS |