Plan Review Notes
Plan Review Notes For Permit 06010091
Permit Number 06010091
Review Stop E
Sequence Number 5
Notes
Date Text
2006-12-20 18:46:26*** UNSAT 5TH REVIEW ***
  
 ** PLEASE SEE NOTES FROM THE FOUR PREVIOUS REVIEWS AS
 FOLLOWS.
 PLEASE CALL IS THERE ARE ANY QUESTIONS OR COMMENTS.
  
  
 1) NOTE:PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW
 DATED 11/16/06. PLEASE SEE THAT THE MANUFACTURES SPECS
 DO NOT CORRELATE WITH THE SAME INFORMATION AS PROVIDED
 ON PLANS. PLEASE SEE THE SPECIFIC UNIT IS NOT CHECKED,
 MARKED, HIGHLIGHTED OR NOTED FOR THE PARTICULAR UNIT.
 PLEASE SEE THE COMMENTS BELOW.
 PLEASE SEE SPECS FOR THE ATS WHICH ARE ONLY NOW BEING
 SUBMITTED FOR REVIEW WOULD STILL NEED TO INDICATE BEING
 3R LISTED AS WELL AS RISER INDICATING THE SAME. 90.7,
 110.3,
 FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTES BELOW FROM REVIEW#4 DATED
 11/16/06 **
 NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE SPECS WERE
 SUBMITTED, HOWEVER AS REQUESTED IN THE PREVIOUS REVIEWS
 PLEASE BE SURE ALL EQUIPMENT CORRELATES FOR USE AND
 INSTALLATION ETC.
 PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A
 FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE
 SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL
 BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN
 SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF
 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES
 MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS
 ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET
 THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE.
 PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE
 ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT
 SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED.
 PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS.
 PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND
 KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS
 THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS
 INDICATES 42KW, AND THE NEED TO CORRELATE THE
 MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF
 THE UTMOST IMPORTANCE.
 PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83"
 LONG, 40" WIDE AND 72" IN HEIGHT.
 PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED
 WE ARE UNABLE TO VERIFY.
 PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF
 THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE
 UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE
 CLEARANCE IF THE UNIT IS 72" HIGH.
 PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE
 AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON
 EQUIPMENT HAVE BEEN SUBMITTED.
 PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS.
  
 ** PLEASE KNOW BASED ON THESE COMMENT FOR THE
 GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY
 NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE
 TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST
 ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED
 TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL
 WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT
 AT THIS TIME.
  
  
 ** PREVIOUS REVIEW COMMENT REVIEW #3**
 PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT
 SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD
 REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES
 WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR
 AND ETC.
 PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT,
 HOWEVER PLEASE SEE PLEASE SUBMIT THE
 MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS,
 AND WP HOUSING.
 PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME
 ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK
 SUBMITTED WHICH DO NOT APPLY AT ALL TO GEN ETC. PLEASE
 SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM FORD
 MOTOR CORP?
 PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS
 BOOKS AND SHEETS AND SOME ARE NOT THE SAME
 EQUIPMENT???
  
 ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT
 SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE
 THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND
 ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND
 STAMPING.
  
 FBC 106.1, 106.1.2, 110.3, 90.7 ETC.
  
 2) NOTE: PLEASE SEE REVIEW NOTE #3 FROM THE PREVIOUS
 REVIEW.
 PLEASE SEE NOT ENERGY CALCULATIONS/LIGHTING POWER
 DENSITIES FOR CODE COMPLIANCE WERE SUBMITTED. PLEASE
 SEE NOTE BELOW WHICH SPEAKS OF THE "BLOCK" LOCATED ON
 PLANS WHICH DID NOT PROVIDE THE INFORMATION AS NEEDED
 AND REQUIRED PER 13-415.1.AB.1, 13-415.2.
  
 *** PREVIOUS REVIEW NOTE REVIEW, REVIEW #4DATED
 11/16/06**
 NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED. THIS
 WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL
 REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE
 REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED
 WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE
 LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE
 THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW.
 PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH
 A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT
 ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY
 REFERENCED.
 PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S)
 AND SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER
 DENSITIES, PER FBC
 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES
 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE
 SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW
 COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE
 LOCATED IN PACKAGE. IN EITHER CASE, PLEASE SUBMIT.
  
  
  
 ** NEW NOTE FOR REVIEW NUMBER 5***
  
 1) NOTE: PLEASE CORRELATE PLANS AND LAYOUT OF
 MAINS/PANELS AND DISCONNECTS ON RISER WITH THAT OF THE
 LAYOUT SHOWN ON E-5.
 PLEASE SEE THE MAIN DISCONNECT FOR THE SECONDARY SIDE
 OF THE TRANSFORMER COULD NOT BE CLEARLY LOCATED.
  
 2) NOTE: PLEASE SEE AS PLANS ARE NOW INDICATING THE
 LOCATION OF ALL EQUIPMENT BEING MOVED TO THE NEW
 LOCATION PLEASE CLARIFY THIS AS THE SUBMITTAL BOOKS FOR
 THE NEW STRUCTURAL MEZZANINE LEVEL FROM PREVIOUS
 SUBMITTED PLANS ARE STILL BEING SUBMITTED. PLEASE SEE
 ANY BUILDING REVIEW COMMENTS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-20 06:52:55REVIEW IN PROGRESS