Plan Review Notes
Plan Review Notes For Permit 06010091
Permit Number 06010091
Review Stop E
Sequence Number 4
Notes
Date Text
2006-11-06 10:40:53*** UNSAT 4TH REVIEW ***
  
 ** PLEASE SEE NOTES FROM THE THREE PREVIOUS REVIEWS AS
 FOLLOWS.
  
  
 1) NOTE:NO, COMMENT NOT FULLY ADDRESSED. PLEASE SEE
 SPECS WERE SUBMITTED, HOWEVER AS REQUESTED IN THE
 PREVIOUS REVIEWS PLEASE BE SURE ALL EQUIPMENT
 CORRELATES FOR USE AND INSTALLATION ETC.
 PLEASE SEE THE ATS SPECS ARE LISTED AND FOR USE FOR A
 FIRE PUMP AND SPECIFIES MANY ITEMS FOR NFPA-20?? PLEASE
 SEE THIS SYSTEM IS PER NFPA-110, 70 AND EQUIPMENT SHALL
 BE LISTED FOR THE INTENDED USE. PLEASE SEE THE GEN
 SPECS NOW SUBMITTED STATE CLEARLY A MINIMUM OF
 3FT/1METER ON ALL SIDES,, HOWEVER AS STATED REQUIRES
 MORE CLEARANCE WHEN INSTALLED IN A WP HOUSING FOR DOORS
 ETC. PLEASE SEE SPACE AS SHOWN DOES NOT SEEM TO MEET
 THE MINIMUM CLEARANCES FOR UNIT WITH THE WP ENCLOSURE.
 PLEASE SEE AS NOTE ON SPECS MENTIONS TO PROVIDE
 ADDITIONAL SPACE FOR DOORS, THIS INFORMATION IS NOT
 SHOWN ON THE ENCLOSURE SPECS AS SUBMITTED.
 PLEASE SEE OTHER COMMENTS FOR VENTILATION IN SPECS.
 PLEASE SEE SPECS DO NOT INDICATE THE SPECIFIC UNIT AND
 KW RATING, NOTE MENTIONS TO SEE NAMEPLATE, HOWEVER AS
 THIS IS NOT POSSIBLE, THE KW RATING AS SHOWN ON PLANS
 INDICATES 42KW, AND THE NEED TO CORRELATE THE
 MANUFACTURES SPECS AND SIZE OF THE UNIT AND WP IS OF
 THE UTMOST IMPORTANCE.
 PLEASE SEE THE CLOSEST UNIT SIZE AND MODEL IS THE 83"
 LONG, 40" WIDE AND 72" IN HEIGHT.
 PLEASE KNOW AS THE UNIT AND ENCLOSURE IS NOT SPECIFIED
 WE ARE UNABLE TO VERIFY.
 PLEASE ALSO SEE AS SHOWN THE EXHAUST IS STRAIGHT OUT OF
 THE TOP AS SHOWN ON HOUSING AND THE SPACE BELOW THE
 UPPER LEVEL FROM THE PARKING DECK DOES NOT PROVIDE
 CLEARANCE IF THE UNIT IS 72" HIGH.
 PLEASE SEE COMMENTS FROM MECHANICAL, PLUMBING AND FIRE
 AND POSSIBLE BLDG COMMENTS NOW THAT THE SPECS ON
 EQUIPMENT HAVE BEEN SUBMITTED.
 PLEASE SEE OTHER COMMENTS WHICH REQUIRE READY ACCESS.
  
 ** PLEASE KNOW BASED ON THESE COMMENT FOR THE
 GENERATOR, AND THE POSSIBILITY THAT THE GENERATOR MAY
 NOT BE PERMITTED TO BE INSTALLED AT THIS LOCATION DUE
 TO MINIMUM CLEARANCES, ACCESS, VENTILATION, EXHAUST
 ETC, PERHAPS THE PERMIT AND PLANS SHOULD ALL BE REVISED
 TO ONLY INCLUDE BUILD OUT OF THE TENANT SPACE AND ALL
 WILL NOT INCLUDE THE GENERATOR OR ASSOCIATED EQUIPMENT
 AT THIS TIME.
  
  
 ** PREVIOUS REVIEW COMMENT REVIEW #3**
 PLEASE KNOW THE FIRST TIME THE MANUFACTURE SPECS/CUT
 SHEETS FOR THE GEN, ETC WERE SUBMITTED ON THE 3RD
 REVIEW AND NOTHING MATCHED. PLEASE SEE PREVIOUS NOTES
 WHICH MENTIONS SPEC SUBMITTED FOR A GASOLINE GENERATOR
 AND ETC.
 PLEASE SEE GEN SUBMITTED IS NOW A LP/NAT GAS UNIT,
 HOWEVER PLEASE SEE PLEASE SUBMIT THE
 MANUFACTURES SPEC/CUT SHEETS FOR THE GENERATOR, ATS,
 AND WP HOUSING.
 PLEASE SEE THAT THIS 3RD REVIEW AND THIS IS FIRST TIME
 ANY PAPER WORK WAS SUBMITTED HOWEVER THERE IS PAPERWORK
 SUBMITTED WHICH DO NOT APPLY AT ALL TO THIS GEN ETC.
 PLEASE SEE "PARTS LIST" BOOK FOR GASOLINE ENGINES FORM
 FORD MOTOR CORP?
 PLEASE SEE WARRANTY BOOKS; PLEASE SEE MULTIPLE ATS
 BOOKS AND SHEETS AND SOME ARE NOT THE SAME
 EQUIPMENT???
  
 ** PLEASE SUBMIT TWO COMPLETE SETS, WITH ONLY PERTINENT
 SHEETS RELEVANT TO THIS INSTALLATION. PLEASE PLACE
 THESE SHEETS INTO SETS BOUND TOGETHER IN A NEAT AND
 ORDERLY FASHION WITH LABELS OR TABS FOR REVIEW AND
 STAMPING.
  
 FBC 106.1, 106.1.2, 110.3, 90.7 ETC.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE SAME NOTE AS PREVIOUSLY STATED.
 THIS WAS REQUIRED AND STATED ON THE FIRST AND ORIGINAL
 REVIEW ON 02/15/06. PLEASE SEE NOTE #10. PLEASE SEE
 REVIEW #2, IT WAS THOUGHT THE CALCULATIONS REQUIRED
 WERE SUBMITTED AND IN PACKAGE, HOWEVER COULD NOT BE
 LOCATED IN 3RD SUBMITTED SETS OR PACKAGE? PLEASE SEE
 THAT THIS WAS PREVIOUSLY STATED ON PREVIOUS REVIEW.
 PLEASE SEE NOW THE RESPONSE IS SHOWING A SMALL BOX WITH
 A FIGURE SHOWN FOR THIS HOWEVER THIS AS SHOWN IS NOT
 ENOUGH AND PLEASE SEE SECTIONS AS PREVIOUSLY
 REFERENCED.
 PLEASE SEE NOTE BELOW WHICH WAS FROM PREVIOUS REVIEW(S)
 AND SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING CALCULATIONS FOR LIGHTING POWER
 DENSITIES, PER FBC
 2004, 13-.AB.1, 13-415.2, 13-415.2.ABC.1, TABLES
 415.2.C.1/415.2.B.1. IT WAS THOUGHT THESE WERE
 SUBMITTED FOR COMPLIANCE WITH THE PREVIOUS REVIEW
 COMMENTS FOR CHAPTER 13, HOWEVER THESE COULD NOT BE
 LOCATED IN PACKAGE. IN EITHER CASE , PLEASE SUBMIT.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-06 07:10:31REMOVED FROM INCOMING. IN ELEC FOR REVIEW.