Plan Review Notes
Plan Review Notes For Permit 06010091
Permit Number 06010091
Review Stop P
Sequence Number 3
Notes
Date Text
2006-10-11 18:50:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. OK
 2. OK - PLANS SHOW TILE TO 4'
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. OK
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****RESPONSE NOTED, BUT GENERATOR SHALL
 VENT OUT OF THE STRUCTURE AND ABOVE THE
 ROOF LEVEL.
 ****NO RESPONSE, NOT ADDRESSED - SEE
 ATTACHED SHEET CONCERNING THE EXHAUST
 FROM THE GENERATOR FROM THE MANUF. SPECIFICATIONS.
 C.OK
 9.OK
 10. OK
 11. OK
 12. OK
  
 **************NEW COMMENT**************
  
 1B. FROM LOOKING AT THE MSDS SHEETS, A
 EYE WASH/EMERGENCY SHOWER WILL BE
 REQUIRED. SECTION 411.
 ****NO RESPONSE, NOT ADDRESSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  