2006-10-11 18:50:47 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. OK |
| 2. OK - PLANS SHOW TILE TO 4' |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| |
| 8. P3 NATURAL GAS RISER. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS |
| PERMIT: |
| A. OK |
| B. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| ****RESPONSE NOTED, BUT GENERATOR SHALL |
| VENT OUT OF THE STRUCTURE AND ABOVE THE |
| ROOF LEVEL. |
| ****NO RESPONSE, NOT ADDRESSED - SEE |
| ATTACHED SHEET CONCERNING THE EXHAUST |
| FROM THE GENERATOR FROM THE MANUF. SPECIFICATIONS. |
| C.OK |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| |
| **************NEW COMMENT************** |
| |
| 1B. FROM LOOKING AT THE MSDS SHEETS, A |
| EYE WASH/EMERGENCY SHOWER WILL BE |
| REQUIRED. SECTION 411. |
| ****NO RESPONSE, NOT ADDRESSED |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |