2006-09-24 00:00:00 | *** UNSAT 3RD REVIEW *** |
| |
| ** PLEASE SEE NOTES FROM THE TWO |
| PREVIOUS REVIEW AS FOLLOWS. |
| |
| |
| 1) NOTE: PLEASE SUBMIT THE |
| MANUFACTURES/SPEC CUT SHEETS FOR THE |
| GENERATOR, ATS, AND WP HOUSING. |
| PLEASE SEE THAT THIS 3RD REVIEW IS FIRST |
| TIME ANY PAPER WORK WAS SUBMITTED, |
| HOWEVER THERE IS PAPERWORK SUBMITTED |
| WHICH DO NOT APPLY AT ALL TO THIS GEN |
| ETC. |
| PLEASE SEE "PARTS LIST" BOOK FOR |
| GASOLINE ENGINES FORM FORD MOTOR CORP? |
| PLEASE SEE WARRANTY BOOKS, PLEASE SEE |
| MULTIPLE ATS BOOKS AND SHEETS AND SOME |
| ARE NOT THE SAME EQUIPMENT??? |
| |
| ** PLEASE SUBMIT TWO COMPLETE SETS, WITH |
| ONLY PERTINENT SHEETS RELEVANT TO THIS INSTALLATION. |
| PLEASE PLACE THIS SHEETS |
| INTO SETS BOUND TOGETHER IN A NEAT AND |
| ODERLY FASHION WITH LABELS OR TABS FOR |
| REVIEW AND STAMPING. |
| |
| FBC 106.1, 106.1.2, 110.3, 90.7 ETC. |
| |
| 2) NOTE: PLEASE SEE THE "S" SHEETS STILL |
| DO NOT CONTAIN THE CORRECT INFORMATION |
| AS REQUIRED UNDER THE FLORIDA |
| ADMINSTRATIVE CODE 61G15-23.002, FLORIDA |
| STATUES 471.023. |
| THIS IS THE 3RD REVIEW FOR THIS NOTE. |
| PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER. PLEASE KNOW, "S" |
| SHEETS MAY BE RETAINED BY THIS OFFICE |
| AND FORWARDED TO THE FBPE'S. |
| |
| 3) NOTE: PLEASE SEE MISSING CALCULATIONS |
| FOR LIGHTING POWER DENSITIES, PER FBC |
| 2004, 13-.AB.1, 13-415.2,13-415.2.ABC.1, |
| TABLES 415.2.C.1/415.2.B.1. IT WAS |
| THOUGHT THESE WERE SUBMITTED FOR |
| COMPLIACNE WITH THE PREVIOUS REVIEW |
| COMMENTS FOR CHAPTER 13, HOWEVER THESE |
| COULD NOT BE LOCATED IN PACKAGE. IN |
| EIHTER CASE , PLEASE SUBMIT. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |