Date |
Text |
2006-08-02 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE ACCESSIBLE. |
| SUBMIT A DETAIL SHOWING THE FOLLOWING: |
| FOR THE W/C |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.4 GRAB BARS |
| D. 11-4.16.5 FLUSH CONTROLS |
| E. 11-4.16.6 DISPENSERS |
| FOR THE LAV |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| FOR THE TOILET ROOM |
| A. 11-4.22.3 A 5' TURNING AREA IS |
| REQUIRED. |
| ****RESPONSE NOTED, BUT ELEVATIONS |
| INDICATED ON SHEET A1, (A7 44, 45), ARE |
| NOT ON SHEET A7. PLEASE CLARIFY. |
| |
| 2. SHT A4 SUBMIT INFORMATION ON THE |
| VINYL WALL PAPER SHOWING COMPLIANCE WITH |
| SECTION 1210.2. WALLS SHALL BE |
| NONABSORBENT. |
| ****RESPONSE NOTED, BUT CODE SECTION |
| 1210.2 STATES "WALLS WITHIN 2FT OF |
| URINALS AND WATER CLOSETS SHALL HAVE A |
| SMOOTH, HARD, NONABSORBENT SURFACE, TO A |
| HEIGHT OF 4 FEET ABOVE THE FLOOR. THE |
| INTENT OF THE CODE IS ALSO FOR CLEAN UP |
| OF THE WALLS. PLEASE SUBMIT A SAMPLE OF |
| THE WALL COVERING SO COMPLIANCE CAN BE DETERMINED. |
| |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| |
| 8. P3 NATURAL GAS RISER. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS |
| PERMIT: |
| A. OK |
| B. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| ****RESPONSE NOTED, BUT GENERATOR SHALL |
| VENT OUT OF THE STRUCTURE AND ABOVE THE |
| ROOF LEVEL. |
| C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****NO MANUF. SPECIFICATION SHEETS |
| SUBMITTED. |
| |
| 9.OK |
| 10. OK |
| 11. OK |
| 12. OK |
| |
| **************NEW COMMENT************** |
| |
| 1B. FROM LOOKING AT THE MSDS SHEETS, A |
| EYE WASH/EMERGENCY SHOWER WILL BE |
| REQUIRED. SECTION 411. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |