2006-07-13 00:00:00 | ***DENIED*** | | | | 1) PLEASE NOTE THAT THE FIRE REVIEW IS | | OK, HOWEVER PLEASE SEE OTHER REVIEW | | COMMENTS REGARDING FS AND FAC | | REQUIREMENTS. | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS TO | | BE MOUNTED AT DISTANCES NOT TO EXCEED | | 75' TRAVEL DISTANCE REQUIREMENT. PLEASE | | ILLUSTRATE ON LS-1. | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|