Date |
Text |
2006-07-02 00:00:00 | *********** UNSAT 2ND REVIEW *********** |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW AND SOME NEW COMMENTS |
| DUE TO SOME MINOR CHANGED ITEMS. |
| |
| ** PLEASE KNOW, PLANS/SUBMITTED |
| MATERIALS ARE NOT COMPLETE AT THIS TIME |
| FOR A COMPLETE REVIEW. |
| |
| ** PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM THE PREVIOUS REVIEW. |
| |
| **************************************** |
| |
| 1A)NOTE: NO , PLEASE SEE SOME SHEETS IN |
| SETS ARE STILL SHOWN WITH SEAL WHICH IS |
| NO LONGER VALID. (S-SHEETS). |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.001 |
| WHICH REQUIRED THE RAISED |
| SEAL TO CHANGE FROM THE WORDING OF |
| "CERTIFICATE" TO "LICENSE" BY 2/5/04, |
| HOWEVER AN EXTENSION WAS GRANTED BY THE |
| FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| TO DECEMBER 31,2005. |
| PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE |
| WORDING ON RAISED SEAL AS REQUIRED. |
| FS 471.025 |
| ANY SEALED PLANS SHALL BECOME "VOID". |
| PLEASE BE SURE THE NEW RAISED SEAL |
| CONTAINS THE "LICENSE" WORDING. |
| PLEASE CONTACT THIS OFFICE OR THE FBPE'S |
| IF THERE ARE ANY QUESTIONS. |
| |
| *************************************** |
| |
| |
| 1) NOTE; OK, HOWEVER SEE NEXT NOTE. |
| |
| 2) NOTE:OK, HOWEVER PLEASE SEE THAT |
| THE 3POLE 125A BRKR ON GEN SHALL BE |
| "SHUNT TRIP" TYPE AND THE SHUNT TRIP |
| BUTTON SHALL BE GROUPED WITH THE OTHER |
| PUSHBUTTONSBEING PROVIDED AT THE FIRST |
| FLR GENERATOR ANNUCIATOR PANEL/FIRE |
| ALARM PANEL LOCATION. |
| |
| ** PREVIOUE NOTE ** |
| PLEASE SEE ALL DISCONNECTING |
| MEANS FOR POWER FEEDERS ETC SHALL BE |
| GROUPED. |
| 230.72,225.31. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE:NO, PLEASE SEE THIS WAS NOT |
| DONE AND REVIEW OF THESE ITEMS CAN NOT |
| BE DONE AT THIS TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT ALL SPECS/MANFACTURES CUT |
| SHEETS FOR GENERATOR, ATS ETC. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE:OK, HOWEVER PLEASE SEE NEW |
| GROUNDING DETAIL FOR TRANSFORMER |
| INDICATES THE NEUTRAL BEING BONDED AT |
| THE TRANSFORMER? PLEASE SEE 250.24B, |
| WHICH REQUIRES THE NEUTRAL TO BE BONDED |
| AT THE FIRST MEANS OF DISCONNECT HOWEVER |
| IN THE SITUATION IT IS PERMITTED. PLEASE |
| SEE THAT BONDING OF THE NEUTRAL IN THE |
| TRANSFORMER WILL THEN REQUIRE ALL |
| GROUNDS AND NEUTRALS TO BE SPLIT AT THE |
| PANEL "P" AND WILL REQUIRE SPECIAL |
| SIGNAGE FOR THE NOTIFICATION FOR NOT TO |
| BOND THE GRND AND THE NEUTRAL BUS AT THE |
| PANEL "P" MCB PANEL. WILL ALSO REQUIRE |
| THE SAME SIGNAGE TO NOTIFY PERSON OF THE |
| BONDING IN THE TRANSFORMER. |
| ** PLEASE KNOW, SIGNAGE AND THE ABOVE |
| SHALL BE PROVIDED, OR THE DETAIL SHOULD |
| NOT HAVE THE NEUTRAL BONDED AT THE |
| TRANSFOMER AND THENEUTRAL AND GRNDS |
| ARE BONDED AT THE PANEL "P" WHICH WOULD |
| BE THE FIRST MEANS OF DISCONNECT. ** *8 |
| THIS OFFICE HAS SEEN THE SCENERIO ON |
| MORE THAN ONE OCCASION WHERE WORK IS |
| BEING PERFORMED IN A PANEL AFTER THE |
| TRANSFORMER AND THE BONDING SCREW OR |
| BONDIGN JUMPER IS ADDED CREATING AN |
| OBJECTIONABLE CURRENT PATH AND |
| PARALLELING THE NEUTRAL. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE PROVIDE GROUNDING |
| ELECTRODE CONNECTION DETAIL(S) FOR THE TRANSFORMER(S). |
| 250.30, 250.58. |
| PLEASE SEE THE CODE SHALL NOT BE |
| REFERENCED IN WHOLE OR IN PART IN LEIU |
| OF THE TECHNICAL INFORMATION REQUIRED ON |
| SAID PLANS. |
| |
| 10)NOTE: OK. |
| |
| 11)NOTE: OK. |
| |
| 12)NOTE: OK. |
| |
| 13)NOTE: NO, THIS IS THE SAME NOTE AND |
| NOTE 1A STILL APPLIES. |
| THESE COMMENTS ARE FOR ALL TRADES AND |
| FOR ALL SHEETS WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT ALL TITLE |
| BLOCKS FOR DESIGNERS OF RECORD CONTAIN |
| ALL LICENSING INFORMATION AS REQUIRED |
| UNDER FAC 61G15-23.002, FS 471.023, THIS |
| COMMENT IS NOT FOR STANDROD ENG.\ |
| PLEASE SEE "S" SHEETS. |
| |
| 14)NOTE: OK. |
| |
| ** PLEASE SEE OTHER COMMENTS FROM OTHER |
| REVIEWERS WHICH WILL AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. THIS WILL HELP TO ALLEAVIATE |
| ANY DELAY'S IN PROJECT. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |