2006-03-13 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE |
| ACCESSIBLE. SUBMIT A DETAIL SHOWING THE |
| FOLLOWING: |
| FOR THE W/C |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.3 HEIGHT |
| C. 11-4.16.4 GRAB BARS |
| D. 11-4.16.5 FLUSH CONTROLS |
| E. 11-4.16.6 DISPENSERS |
| FOR THE LAV |
| A. 11-4.19.2 HEIGHT & CLEARANCES |
| B. 11-4.19.3 CLEAR FLOOR SPACE |
| C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| D. 11-4.19.5 FAUCETS |
| FOR THE TOILET ROOM |
| A. 11-4.22.3 A 5' TURNING AREA IS |
| REQUIRED. |
| 2. SHT A4 SUBMIT INFORMATION ON THE |
| VINAL WALL PAPER SHOWING COMPLIANCE WITH |
| SECTION 1210.2. WALLS SHALL BE |
| NONABSORBENT. |
| 3. SHTS A6 & A7 TOILET ROOM DETAILS 7 |
| THRU 10, 22, 23, 26, 27, 34 THRU 37. |
| SHOW THE FOLLOWING: |
| FOR THE LAVS |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| 4. SHT A6 DETAIL #11 SHOW THE FOLLOWING: |
| FOR THE DRINKING FOUNTAIN: |
| A. 11-4.15.2 SPOUT |
| B. 11-4.15.3 SPOUT LOCATION |
| C. 11-4.15.4 CONTROLS |
| D. 11-4.19.5 CLEARANCES & CLEAR FLOOR |
| SPACE. |
| 5. SHT A7 DETAILS 30 & 32 SHOW THE |
| FOLLOWING FOR THE SINKS. |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD |
| APPROACH REQUIRED. CABINET DOORS TO BE |
| REMOVED AS THEY CAN NOT BE IN THE CLEAR |
| FLOOR SPACE) |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| 6. ALL PME SHEETS THAT WILL BE |
| RESUBMITTED SHALL HAVE THE NEW SEALS PER |
| FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| RULE. (SEE ATTACHED SHEET). |
| 7. SHT P1 CODE REFERENCED IS FBC-2001. |
| WE HAVE ADOPTED FBC-2004 SINCE 10-01-05 |
| AND ALL PLANS SHALL BE DESIGNED TO THE |
| FBC-2004 AND PLANS SHALL REFERENCE THE |
| 2004 CODE AS WELL. |
| 8. P3 NATURAL GAS RISER. THE FOLLOWING |
| INFORMATION IS REQUIRED FOR THE GAS |
| PERMIT: |
| A. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| B. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| 9. SHT P3 GAS RISER NOTE #1 REFERENCES |
| FBC-2001 FUEL GAS CODE. GAS CODE IN |
| EFFECT IS FBC-2004 FUEL GAS. PLEASE |
| CHANGE REFERENCE, AND DESIGN TO THE |
| PROPER CODE. |
| 10. SHT P4 FLOOR DRAINS ARE NOT APPROVED |
| INDIRECT WASTE RECEPTORS. A FLOOR SINK |
| OR A HUB DRAIN IS REQUIRED. SECTIONS |
| 803.2 AND 802.3.2. |
| 11. SHT P4 DOMESTIC WATER ISOMETRIC |
| RISER. WATER HAMMER ARRESTORS REQUIRED |
| BY SECTION 604.9 AT THE WASH MACHINE |
| SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| SHOWN. PDI-WH 201 AND MANUFACTURE |
| INSTALLATION INSTRUCTIONS. |
| 12. SHT P4 WATER RISER DIAGRAM, FULL |
| OPEN VALVES ARE REQUIRED AT THE TOP OF |
| ALL WATER DOWN-FEED PIPES. SECTION |
| 606.1(4). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |