Plan Review Notes
Plan Review Notes For Permit 06010091
Permit Number 06010091
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-13 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A1 ROOM 108 STAFF TOILET SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING THE
 FOLLOWING:
 FOR THE W/C
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR THE LAV
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 FOR THE TOILET ROOM
 A. 11-4.22.3 A 5' TURNING AREA IS
 REQUIRED.
 2. SHT A4 SUBMIT INFORMATION ON THE
 VINAL WALL PAPER SHOWING COMPLIANCE WITH
 SECTION 1210.2. WALLS SHALL BE
 NONABSORBENT.
 3. SHTS A6 & A7 TOILET ROOM DETAILS 7
 THRU 10, 22, 23, 26, 27, 34 THRU 37.
 SHOW THE FOLLOWING:
 FOR THE LAVS
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 4. SHT A6 DETAIL #11 SHOW THE FOLLOWING:
 FOR THE DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.19.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 5. SHT A7 DETAILS 30 & 32 SHOW THE
 FOLLOWING FOR THE SINKS.
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED. CABINET DOORS TO BE
 REMOVED AS THEY CAN NOT BE IN THE CLEAR
 FLOOR SPACE)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 6. ALL PME SHEETS THAT WILL BE
 RESUBMITTED SHALL HAVE THE NEW SEALS PER
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 RULE. (SEE ATTACHED SHEET).
 7. SHT P1 CODE REFERENCED IS FBC-2001.
 WE HAVE ADOPTED FBC-2004 SINCE 10-01-05
 AND ALL PLANS SHALL BE DESIGNED TO THE
 FBC-2004 AND PLANS SHALL REFERENCE THE
 2004 CODE AS WELL.
 8. P3 NATURAL GAS RISER. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
 A. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 9. SHT P3 GAS RISER NOTE #1 REFERENCES
 FBC-2001 FUEL GAS CODE. GAS CODE IN
 EFFECT IS FBC-2004 FUEL GAS. PLEASE
 CHANGE REFERENCE, AND DESIGN TO THE
 PROPER CODE.
 10. SHT P4 FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK
 OR A HUB DRAIN IS REQUIRED. SECTIONS
 803.2 AND 802.3.2.
 11. SHT P4 DOMESTIC WATER ISOMETRIC
 RISER. WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9 AT THE WASH MACHINE
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUFACTURE
 INSTALLATION INSTRUCTIONS.
 12. SHT P4 WATER RISER DIAGRAM, FULL
 OPEN VALVES ARE REQUIRED AT THE TOP OF
 ALL WATER DOWN-FEED PIPES. SECTION
 606.1(4).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS