Plan Review Notes For Permit 06010091 |
Permit Number |
06010091 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-09 00:00:00 | PLAN DENIED | | 1- PLEASE PROVIDE A UL LISTED FLOOR | | PENETRATION ASSEMBLY FOR THE REFRIGERANT | | LINES ON A/C 1,2. | | 2- PLEASE PROVIDE A COPY OF THE | | MANUFACTURERS INSTALLATION INSTRUCTIONS | | FOR THE GENERATOR. | | 3- PLEASE PROVIDE ON THE PLANS THE TYPE | | OF FUEL USED FOR THE GENERATOR.LOCATION | | OF FILL PIPE AND VENT LINE. AND LOCATION | | OF FUEL TANK IF THERE IS ONE. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|