Plan Review Notes For Permit 06010091 |
Permit Number |
06010091 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-13 00:00:00 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. P3 NATURAL GAS RISER. THE FOLLOWING | | INFORMATION IS REQUIRED FOR THE GAS | | PERMIT: | | A. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304. | | B. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|