2006-03-01 00:00:00DENIED:
  
 1) THIS PROJECT SHALL COMPLY WITH NFPA
 101 LIFE SAFETY CODE, 2003 EDITION AND
 NFPA 1 UNIFORM FIRE CODE, 2003 EDITION.
  
 2) ON SHEET A1 DOOR #182 SHOULD SWING IN
 THE DIRECTION OF TRAVEL.
  
 3) PLEASE PROVIDE CUT SHEETS AND SPEC'S
 ON EQUIPMENT BEING INSTALLED.
  
 4) THE GENERATOR IS NOT PERMITTED ON 6TH
 FLOOR, PLEASE REFERENCE AND COMPLY WITH
 NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS, 2002 EDITION, FOR
 LOCATION, INSTALLATION, AND OTHER
 REQUIREMENT.
  
 5) PLEASE REFERENCE AND COMPLY WITH NFPA
 801 STANDARD FOR FIRE PROTECTION FOR
 FACILITIES HANDLING RADIOACTIVE
 MATERIALS, 1998 EDITION. ( X-RAY,
 MAGNETIC, AND NUCLEAR EQUIPMENT )
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL