Plan Review Notes For Permit 06010091 |
Permit Number |
06010091 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-01 00:00:00 | DENIED: | | | | 1) THIS PROJECT SHALL COMPLY WITH NFPA | | 101 LIFE SAFETY CODE, 2003 EDITION AND | | NFPA 1 UNIFORM FIRE CODE, 2003 EDITION. | | | | 2) ON SHEET A1 DOOR #182 SHOULD SWING IN | | THE DIRECTION OF TRAVEL. | | | | 3) PLEASE PROVIDE CUT SHEETS AND SPEC'S | | ON EQUIPMENT BEING INSTALLED. | | | | 4) THE GENERATOR IS NOT PERMITTED ON 6TH | | FLOOR, PLEASE REFERENCE AND COMPLY WITH | | NFPA 110 STANDARD FOR EMERGENCY AND | | STANDBY POWER SYSTEMS, 2002 EDITION, FOR | | LOCATION, INSTALLATION, AND OTHER | | REQUIREMENT. | | | | 5) PLEASE REFERENCE AND COMPLY WITH NFPA | | 801 STANDARD FOR FIRE PROTECTION FOR | | FACILITIES HANDLING RADIOACTIVE | | MATERIALS, 1998 EDITION. ( X-RAY, | | MAGNETIC, AND NUCLEAR EQUIPMENT ) | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|