2006-02-15 00:00:00 | *********** UNSAT *************** |
| |
| ** PLEASE KNOW, PLANS/SUBMITTED |
| MATERIALS ARE NOT COMPLETE AT THIS TIME |
| FOR A COMPLETE REVIEW. |
| |
| **************************************** |
| |
| 1A)NOTE: PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.001 WHICH |
| REQUIRED THE RAISED SEAL TO CHANGE FROM |
| THE WORDING OF "CERTIFICATE" TO |
| "LICENSE" BY 2/5/04, HOWEVER AN |
| EXTENSION WAS GRANTED BY THE FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS TO |
| DECEMBER 31,2005. |
| PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE |
| WORDING ON RAISED SEAL AS REQUIRED. |
| FS 471.025 |
| ANY SEALED PLANS SHALL BECOME "VOID". |
| PLEASE BE SURE THE NEW RAISED SEAL |
| CONTAINS THE "LICENSE" WORDING. |
| PLEASE CONTACT THIS OFFICE OR THE FBPE'S |
| IF THERE ARE ANY QUESTIONS. |
| |
| *************************************** |
| |
| |
| 1)NOTE; PLEASE SEE LOCATION OF GENERATOR |
| LOCATED ON THE 6TH LEVEL IS NOT |
| PERMITTED BY THIS OFFICE AND FIRE |
| MARSHAL'S OFFICE. |
| PLEASE ALSO SEE ELECTRICAL COMMENTS |
| PERTAINING LOCATION OF DISCONNECTING |
| ETC. |
| |
| 2)NOTE: PLEASE SEE ALL DISCONNECTING |
| MEANS FOR POWER FEEDERS ETC SHALL BE |
| GROUPED. |
| 230.72,225.31. |
| |
| 3)NOTE: PLEASE BE SURE PLANS REFERENCE |
| THE FOLLOWING APPLICABLE CODES, 2002 |
| NFPA-70, 2003 NFPA-101, 2002 NFPA-72, |
| 2002 NFPA-110, 1999 NFPA-75 |
| |
| 4)NOTE: PLEASE SUBMIT ALL |
| SPECS/MANFACTURES CUT SHEETS FOR |
| GENERATOR, ATS ETC. |
| IF THE EPSS IS GOING TO BE INSTALLED |
| UNDER THIS PERMIT, PLEASE INCLUDE. |
| |
| 5)NOTE: PLEASE SEE 645.10,,300.21 FOR |
| LOCATION AND SHUT DOWN OF ELECTRICAL |
| REQUIRED FOR A/C'S AND ALL ALL EQUIPMENT |
| FEEDING IT ROOM. |
| PLEASE SEE A/C SYSTEMS. |
| |
| 6)NOTE: PLEASE SEE 645.5D FOR SD'S AND |
| DETAILS REQUIRED FOR REVIEW AND |
| CONNECTION INTO THE FA SYSTEM. |
| |
| 7) NOTE: PLEASE SHOW AND IDENTIFY AL |
| REQUIREMENTS FOR THE IT ROOM AND |
| REFERENCE NFPA-75 ON ALL P,M, E, |
| ARCHITECTUAL AND STRUCTUAL PLANS. |
| ALL CONTRUCTION, FIRE SPRINKLER |
| PROTECTION AND OR OTHER EXTINGUISHING |
| SYSTEMS SHALL BE PROVIDED. |
| PLEASE MAKE REFERENCE TO THE ROOM |
| PENETRATIONS AS REQUIRED PER CHAPTER 3. |
| ETC |
| |
| 8)NOTE: PLEASE SEE THAT AN EM BATTERY |
| BACK LT OF SOME SORT BE PROVIDED IN THE |
| ELECTRICAL ROOM. |
| 700.16, 101,7.8,7.9 ETC. |
| |
| 9)NOTE: PLEASE PROVIDE GROUNDING |
| ELECTRODE CONNECTION DETAIL(S) FOR THE |
| TRANSFORMER(S). 250.30, 250.58. |
| PLEASE SEE THE CODE SHALL NOT BE |
| REFERENCED IN WHOLE OR IN PART IN LEIU |
| OF THE TECHNICAL INFORMATION REQUIRED ON |
| SAID PLANS. |
| |
| 10)NOTE: PLEASE SEE THE FBC 2004 CHAPTER |
| 13. PLEASE SEE 13-413.1ABC.1 FOR VOLTAGE |
| DROP OF FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1 FOR LIGHTING |
| CONTROL OF SPCES. |
| TANDEM WIRING PER 13-415.1.ABC.3, .4 |
| PLEASE SEE ALL OF CHAPTER 13 FOR |
| COMMERCIAL SPACES. |
| |
| 11)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| ON PLANS WITH TEH SUBMITTED PANEL |
| SCHEDULES. |
| PLEASE SEE MANY WSH UNITS, A/C 1&2 UNITS |
| ETC. |
| 215.5 |
| |
| 12)NOTE: PLEASE PROVIDE IDENTIFICATION |
| ON PLANS FOR ALL FIXTURES AND CORRELATE |
| WITH THE FIXTURE LEGEND SUBMITTED. |
| |
| 13)NOTE: PLEASE SEE THAT ALL TITLE |
| BLOCKS FOR DESIGNERS OF RECORD CONTAIN |
| ALL LICENSING INFORMATION AS REQUIRED |
| UNDER FAC 61G15-23.002, FS 471.023, THIS |
| COMMENT IS NOT FOR STANDROD ENG.\ |
| PLEASE SEE "S" SHEETS. |
| |
| 14)NOTE: PLEASE SEE THE COMPLETE |
| VALUATION FOR SCOPE OF WORK SHALL |
| INCLUDE ALL LABOR AND MATERIALS, EVEN IF |
| EQUIPMENT IS OWNER SUPPLIED. PLEASE SEE |
| ANY SYSTEM PERMANANTLY INSTALLED, |
| HARDWIRED , FASTENED IN PLACE SHALL BE |
| INCLUDED. |
| FBC ADMINISTRATIVE SECTION 108.3. AS |
| ADOPTED BY THE CITY OF WEST PALM BEACH. |
| |
| ** PLEASE SEE OTHER COMMENTS FROM OTHER |
| REVIEWERS WHICH WILL AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. THIS WILL HELP TO ALLEAVIATE |
| ANY DELAY'S IN PROJECT. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |