Date |
Text |
2006-01-30 00:00:00 | *** DENIED *** |
| 1)ENERGY CALCULATIONS NEED TO BE ON FORM |
| 600A-04 (2004) PER FBC 13-600.3.A . |
| |
| 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| BY OWNER/AGENT. |
| |
| 3) 2ND. FLOOR RAG 18X8, IF THIS IS A |
| TRANSFER GRILL IT IS TO SMALL FOR THE |
| AMOUNT OF SUPPLY AIR TO THE ROOM SEE |
| NOTE #4. |
| |
| BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 5) PLEASE SHOW ON MECHANICAL PLANS HOW |
| RETURN AIR IS BEING PROVIDE FOR 1 ST. |
| FLOOR EXISTING HOUSE. |
| |