Plan Review Notes
Plan Review Notes For Permit 06010060
Permit Number 06010060
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00******DENIED******
  
 1) CODE INFORMATION INDICATES AN
 OCCUPANT LOAD OF 308. PLEASE NOTE THAT A
 FIRE ALARM SYSTEM IS REQUIRED IN
 ASSEMBLY OCCUPANCIES WITH OCCUPANT LOAD
 OF 300 OR MORE.
  
 2) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED REGARDING LIFE SAFETY.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR BOTH THE FIRE SPRINKLER
 REMODEL AND FIRE ALARM SYSTEM. FIRE
 ALARM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR NEW HANDRAILS AND
 GUARDS.
  
 6) PLEASE ILLUSTRATE ALL NEW OR EXISTING
 EXIT LIGHT AND EMERGENCY LIGHT
 LOCATIONS.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL MEET THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 8) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 9) PLEASE PROVIDE MORE INFORMATION/FLAME
 RETARDANT FOR CANVAS ROOF.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722