Plan Review Notes For Permit 06010060 |
Permit Number |
06010060 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-07 00:00:00 | ******DENIED****** | | | | 1) CODE INFORMATION INDICATES AN | | OCCUPANT LOAD OF 308. PLEASE NOTE THAT A | | FIRE ALARM SYSTEM IS REQUIRED IN | | ASSEMBLY OCCUPANCIES WITH OCCUPANT LOAD | | OF 300 OR MORE. | | | | 2) NFPA 101, 2003 EDITION SHALL BE | | REFERENCED REGARDING LIFE SAFETY. | | | | 3) CONSTRUCTION, ALTERATION AND | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR BOTH THE FIRE SPRINKLER | | REMODEL AND FIRE ALARM SYSTEM. FIRE | | ALARM TO BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE. | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | REQUIREMENTS FOR NEW HANDRAILS AND | | GUARDS. | | | | 6) PLEASE ILLUSTRATE ALL NEW OR EXISTING | | EXIT LIGHT AND EMERGENCY LIGHT | | LOCATIONS. | | | | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED AND SHALL MEET THE 75' TRAVEL | | DISTANCE REQUIREMENT. | | | | 8) PLEASE INDICATE MINIMUM INTERIOR | | FINISH CLASSIFICATION FOR WALLS AND | | CEILINGS. | | | | 9) PLEASE PROVIDE MORE INFORMATION/FLAME | | RETARDANT FOR CANVAS ROOF. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|