2006-03-29 00:00:00 | ****** UNSAT ******* |
| |
| 1) NOTE: PLEASE SEE NOTE MENTIONS "NEW |
| LIGHT" ? HOWEVER NO NEW LIGHTS WERE |
| FOUND ON PLANS?? |
| PLEASE CLARIFY NEW EGRESS LIGHTING PER |
| NFPA-101 7.8,7.9. |
| PLEASE KNOW, BATTERY BACK UP FIXTURE OF |
| SOME SORT WILL BE REQUIRED TO ILLUMINATE |
| EGRESS TO THE PUBLIC RIGHT OF WAY. IF |
| EXISTING, PLEASE SHOW. |
| |
| 2)NOTE: PLEASE COMPLETE CIRCUITING ON |
| PLANS FOR NEW 20A CIRCUITS AS NOTED. |
| PLEASE SEE NO CONTROL OF FANS, OR WHERE |
| "J-BOXES" ARE FED, CONTROLS? LIGHTS? GFI |
| ? IF CIRCUITS FOR ALL OF WHAT IS BEING |
| SHOWN ARE COMING FROM THESE TWO NEW 20A |
| CIRCUITS, THEN, SHOW WHICH CIRCUIT IS |
| FEEDING WHICH DEVICE. |
| PLEASE INDICATE THE SPARE SPACES AND |
| PANEL THESE ARE COMING FROM. |
| 215.5 |
| |
| |
| ** PLEASE SEE COMMENTS FROM BLDG REVIEW, |
| AS STRUCTURAL ENGINEER LISTED ON COVER |
| SHEET IS NOT THE ENGINEER ON PLANS. |
| THIS IS NOT AN ELECTRICAL REVIEW |
| COMMENT. |
| |
| ** PLEASE SEE ANY NOTES FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE COMPLETELYREMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |