Plan Review Notes
Plan Review Notes For Permit 06010031
Permit Number 06010031
Review Stop B
Sequence Number 1
Notes
Date Text
2006-01-03 00:00:001) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
  
  
 __X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.PLEASE SELECT A SYSTEM
 FROM THE NOA PACKAGE FOR REVIEW.THE
 FIRST FEW PAGES WHICH LIST THE DIFFERENT
 MATERIALS ARE REQUIRED ALONG WITH ONE OF
 THE SYSTEMS WHICH WILL BE USED.SUBMIT
 TWO COPIES OF THE NOA NOT ONE.
  
 2) FBC 1606.2.5.GENERAL LIMITATION
 #9 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  