Plan Review Notes
Plan Review Notes For Permit 05121266
Permit Number 05121266
Review Stop B
Sequence Number 1
Notes
Date Text
2006-01-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)THIS BUILDING WAS DESIGNED AS 145
 MPH, EXPOSURE C.USING FBC TABLE
 1606.2B, THE LIMITATION OF -52.5 DOES
 NOT MEET THE MINIMUM DESIGN PRESSURE
 REQUIREMENT.SELECT A COMPLIANT
 ASSEMBLY AND HAVE THE PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD TO
 CONFIRM THAT DESIGN CRITERIA HAVE BEEN
 MET OR EXCEEDED.