Plan Review Notes
Plan Review Notes For Permit 05121233
Permit Number 05121233
Review Stop P
Sequence Number 3
Notes
Date Text
2006-03-31 00:00:00 
  
  
  
 ******PROVISO******
 604.9 WATER HAMMER. THE FLOW VELOCITY OF
 THE WATER DISTRIBUTION SYSTEM SHALL BE
 CONTROLLED TO REDUCE THE POSSIBILITY OF
 WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING
 VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURE'S
 SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
 *********************************