2006-01-24 00:00:00 | DENIED; | | 1. SANITARY RISER DIAGRAM DOESNOT MATCH | | FLOOR PLAN. | | 2.RISER DIAGRAM SHOWS 2- TUBS NO SHOWER. | | 3.RISER DIAGRAM SHOWS 2 WASHERS. | | 4.W/M AND L/T CANNOT DISCHARGE INTO A | | BATHROOM GROUP. MUST BE DOWN STREAM OF | | BATHROOM. FBC-2004 SEC. 909.1. | | 5.WATER HEATER SHOULD NOT BE SHOWN ON | | SAN.RISER. | | 6.VENTING ON SAN.RISER IS NOT TO CODE. | | 7.AIRCHAMMBERS ARE NOT TO CODE, MUST BE | | WATER HAMMER ARRESTORS TO BE INSTALL PER | | FBC-2004 PLUMBING SEC.604.9. | | 8. THE BRANCH DRAIN TO THE W/M MUST BE | | 3" PER SEC.406.3. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|