Plan Review Notes
Plan Review Notes For Permit 05121233
Permit Number 05121233
Review Stop P
Sequence Number 1
Notes
Date Text
2006-01-24 00:00:00DENIED;
 1. SANITARY RISER DIAGRAM DOESNOT MATCH
 FLOOR PLAN.
 2.RISER DIAGRAM SHOWS 2- TUBS NO SHOWER.
 3.RISER DIAGRAM SHOWS 2 WASHERS.
 4.W/M AND L/T CANNOT DISCHARGE INTO A
 BATHROOM GROUP. MUST BE DOWN STREAM OF
 BATHROOM. FBC-2004 SEC. 909.1.
 5.WATER HEATER SHOULD NOT BE SHOWN ON
 SAN.RISER.
 6.VENTING ON SAN.RISER IS NOT TO CODE.
 7.AIRCHAMMBERS ARE NOT TO CODE, MUST BE
 WATER HAMMER ARRESTORS TO BE INSTALL PER
 FBC-2004 PLUMBING SEC.604.9.
 8. THE BRANCH DRAIN TO THE W/M MUST BE
 3" PER SEC.406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695