2008-05-28 16:39:32REVIEW #: REVISION 5
 ACTION: PAGES M4.1 AND M5.1 DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PG M4.1 AND M5.1: MECHANICAL ROOM FLOOR PLANS ON M4.1
 AND SHAFT RISER DIAGRAMS ON M5.1 SHOW DUCT PENETRATIONS
 OF SHAFTS PROTECTED WITH FIRE DAMPERS. SHAFT ENCLOSURES
 THAT ARE PERMITTED TO BE PENETRATED BY DUCTS AND AIR
 TRANSFER OPENINGS SHALL BE PROTECTED WITH APPROVED FIRE
 AND SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING PER FBCM 607.5.5.1. SHOW THESE DUCT
 PENETRATIONS TO BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH THIS SECTION.
  
 ALSO, PLEASE SHOW HOW THESE SMOKE DAMPERS ARE TO BE
 CONTROLLED AND ACTUATED IN ACCORDANCE WITH FBCM
 607.3.2.1.
  