2007-03-08 19:01:59 | DENIED BY BUILDING |
| |
| 2004 FLORIDA BUILDING CODE |
| 4 STORY OFFICE BUILDING (SHELL) |
| TYPE II-B (SPRINKLERED) |
| BUSINESS OCCUPANCY |
| FLOOD ZONE A9 BFE 13' (+6" CITY REQ) |
| REQUIRED SOIL BEARING CAPACITY 2500 AND |
| 8000 PSF |
| |
| NOTE: STRUCTURE IS LOCATED IN AN A9 FLOOD |
| ZONE. AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. WORK MUST COMMENCE WITHIN 90 DAYS |
| OF RECORDING DATE. THE ONE SUBMITTED WILL NEED TO BE |
| RE-RECORDED. |
| |
| 2)A PAID IN FULL RECEIPT IS REQUIRED BEFORE PERMIT |
| CAN BE ISSUED. |
| |
| 3) THE MAXIMUM DESIGN PRESSURE FROM THE MODIFIED |
| ROOFING PRODUCT APPROVAL IS TOO LOW BASED ON THE ROOF |
| PRESSURES ON PAGE S12 OF PLANS. THE PRODUCT APPROVAL |
| ALLOWS FOR INCREASED PRESSURES THROUGH ENHANCED |
| FASTENING (SEE LIMITATION #7 ON NOA) WITH SIGNED AND |
| SEALED RAS 117 CALCULATIONS.PLEASE SUBMIT THE SIGNED |
| AND SEALED RAS 117 CALCULATIONS. |
| PER YOUR RESPONSE THIS WILL BE A PROVISO ITEM, UNTIL |
| AFTER A PULL TEST IS COMPLETED ON THE LIGHT WEIGHT ROOF |
| INSULATION. |
| |
| 4)FBC 1406.2.2REQUIRES ARCHITECTURAL TRIM THAT |
| EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE |
| SHALL BE CONSTRUCTED OF APPROVED NONCOMBUSTIBLE |
| MATERIALS AND SHALL BE SECURED TO THE WALL WITH METAL |
| OR OTHER APPROVED NONCOMBUSTIBLE BRACKETS. FOAM BANDING |
| AT PARAPET AND MEDALLIONS AS SHOWN ON A3.1.1 ARE |
| NON-COMPLIANT. DETAIL 19 ON 5.1.1 IS LABELED TYPICAL |
| FOAM BANDING. |
| |
| 5) ONE OF THE PLANS IS MISSING SHEETS A9.1.2 AND |
| A3.2.1. |
| |
| 6) THE DOOR SCHEDULE SPECIFIES A 20 MINUTE FIRE RATED |
| DOOR AT THE ROOF FOR DOOR # 525. THIS IS A 2 HOUR RATED |
| STAIR SHAFT. A 90 MINUTE RATED DOOR IS REQUIRED. |
| |
| 7) SHEET A2.1.2IS TITLED SECOND-FOURTH FLOOR PLANS. |
| THE DRAWING INDEX SPECIFIES SECOND -THIRD FLOOR FOR |
| A2.1.2. THE DOOR SCHEDULE ON A8.1.1 LISTS DOORS FOR THE |
| FORTH FLOOR. PLEASE CLARIFY. |
| |
| 8) THE PRODUCT APPROVAL FROM YKK AP AMERICA, INC. FOR |
| THE YHS-50 STOREFRONT (NOA 02-0215.17 HAS MULLION |
| CAPACITY PRESSURES TOO LOW FOR WINDOWS A & E (+45.5 / |
| -45.6 PSF)AND WINDOWS B AND F (+65 / - 65 PSF). SEE |
| REQUIRED PRESSURES ON SHEET S12. |
| |
| 9) THE PRODUCT APPROVAL FROM MILLER GLASS AND GLAZING |
| FOR THE STOREFRONTS HAS PRESSURES THAT ARE TOO LOW FOR |
| SOME OF THE PRESSURE ZONES SPECIFIED ON THE PLANS. |
| THERE ARE TWO DRAWINGS FOR LARGE MISSILE IMPACT, ONE |
| WITH MAXIMUM FRAME HEIGHT OF 86-1/2"WITH A HORIZONTAL |
| MULLION (+58 /-65 PSF)AND ONE WITH MAXIMUM FRAME |
| HEIGHT OF 108" WITH HORIZONTAL MULLION ( + 60 / - 65). |
| THE FRAME HEIGHT FOR WINDOWS A AND E IS 116". THE OTHER |
| DRAWING IS FOR SMALL MISSILE IMPACT WITH MAXIMUM FRAME |
| HEIGHT OF 86-1/2" FRAME HEIGHT (+60 / -67). |
| |
| 10) THE SECTION OF EXTERIOR WALL ON THE EAST ELEVATION |
| THAT IS LESS THAN 10 FEET FROM THE CONDO PROPERTY LINE |
| (FIRE SEPARATION DISTANCE) IS REQUIRED BY FBC TABLE 602 |
| TO HAVE A ONE HOUR FIRE RATING FOR TYPE II-B |
| CONSTRUCTION. IN ADDITION, FBC TABLE 704.8 LIMITS THE |
| ALLOWABLE AREA OF UNPROTECTED OPENINGS TO 10% OF THE |
| WALL AREA. PER YOUR COMMENTS, FBC 704.8.1 DOES ALLOW |
| UNPROTECTED WALL OPENINGS OF 25% OF THE WALL AREA |
| BECAUSE THE BUILDING IS FULLY SPRINKLERED IN ACCORDANCE |
| WITH FBC 903.3.1.1.HOWEVER, YOUR CALCULATIONS OF WALL |
| AREA APPEAR TO HAVE INCLUDED THE AREA OF THE PARAPET |
| WALL, WHICH SHOULD NOT BE INCLUDED. SEE FBC CHAPTER 2 |
| FOR DEFINITIONS OF STORY. THAT PORTION OF A BUILDING |
| INCLUDED BETWEEN THE UPPER SURFACE OF A FLOOR AND THE |
| UPPER SURFACE OF THE FLOOR OR ROOF NEXT ABOVE (ALSO SEE |
| "BASEMENT," "MEZZANINE" AND SECTION 502.1 ). IT IS |
| MEASURED AS THE VERTICAL DISTANCE FROM TOP TO TOP OF |
| TWO SUCCESSIVE TIERS OF BEAMS OR FINISHED FLOOR |
| SURFACES AND, FOR THE TOPMOST STORY, FROM THE TOP OF |
| THE FLOOR FINISH TO THE TOP OF THE CEILING JOISTS OR, |
| WHERE THERE IS NOT A CEILING, TO THE TOP OF THE ROOF |
| RAFTERS. 52' X 60' 5-1/2" = 3,143.92 SQFT X 25% = |
| 785.98 SQFT OF OPENINGS ALLOWED. |
| |