Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop B
Sequence Number 3
Notes
Date Text
2007-01-05 09:42:33DENIED BY BUILDING
  
 2004 FLORIDA BUILDING CODE
 4 STORY OFFICE BUILDING (SHELL)
 TYPE II-B (SPRINKLERED)
 BUSINESS OCCUPANCY
 FLOOD ZONE A9 BFE 13' (+6" CITY REQ)
 REQUIRED SOIL BEARING CAPACITY 2500 AND
 8000 PSF
  
 1) STRUCTURE IS LOCATED IN AN A9 FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) PRIOR TO PERMIT ISSUANCE, PLEASE ARRANGE WITH HAROLD
 PISKURA (INSPECTION SERVICES MANAGER - TEL :
 561-805-6711), A MEETING INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER.
  
 5) ON SHEET A2.0.1 UNDER CODE ANALYSIS/ APPLICABLE
 CODES, THE HIGH VELOCITY HURRICANE ZONES IS INCORRECTLY
 SPECIFIED. THIS PROJECT IS NOT LOCATED WITHIN THE HIGH
 VELOCITY HURRICANE ZONE.
  
 6) ON SHEET A1.1.1, THE DETAIL TAGS SPECIFY THE WRONG
 PAGES. IT SHOULD BE PAGE A1.2.4.
  
 7) THE MAXIMUM DESIGN PRESSURE FROM THE MODIFIED
 ROOFING PRODUCT APPROVAL IS TOO LOW BASED ON THE ROOF
 PRESSURES ON PAGE S12 OF PLANS. THE PRODUCT APPROVAL
 ALLOWS FOR INCREASED PRESSURES THROUGH ENHANCED
 FASTENING (SEE LIMITATION #7 ON NOA) WITH SIGNED AND
 SEALED RAS 117 CALCULATIONS.PLEASE SUBMIT THE SIGNED
 AND SEALED RAS 117 CALCULATIONS.
  
 8)THE FIRE WINDOWS IN WATER PUMP ROOM ARE NOT CODE
 COMPLIANT. FBC 715.4 REQUIRES FIRE-PROTECTION-RATED
 GLAZING IN INTERIOR ONE HOUR RATED WALLS TO HAVE A 45
 MINUTE RATING. THE FIRE GLASS 20 SPECIFIED IN DETAIL 1
 ON A8.1.1 HAS A TWENTY MINUTE FIRE RATING. FBC
 715.4.7.2LIMITS THE TOTAL AREA OF INTERIOR FIRE
 WINDOW ASSEMBLIES TO NOT EXCEED 25 PERCENT OF THE AREA
 OF A COMMON WALL WITHIN ANY ROOM. THE ALLOWABLE AREA
 FOR FIRE WINDOWS IS EXCEEDED.
  
 9) THE STATE PRODUCT APPROVAL COVERSHEET FOR THE
 WINDSOR REPUBLIC DOOR DOES NOT CORRESPOND THE THE
 ATTACHED NOA FOR THE SERIES DM 418 STEEL DOOR. PLEASE
 CORRECT.
  
 10) THE OTHER PRODUCT APPROVALS SUBMITTED DO NOT HAVE
 THE STATE PRODUCT APPROVAL COVERSHEETS WITH THEFL#
 ATTACHED. NOTE: FBC* 109.3.6 REQUIRES THE PRODUCT
 APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 11)FBC 1406.2.2REQUIRES ARCHITECTURAL TRIM THAT
 EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE
 SHALL BE CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS AND SHALL BE SECURED TO THE WALL WITH METAL
 OR OTHER APPROVED NONCOMBUSTIBLE BRACKETS. FOAM BANDING
 AT PARAPET AND MEDALLIONS AS SHOWN ON A3.1.1 ARE
 NON-COMPLIANT.
  
 12)A SEPARATE PERMIT WILL BE REQUIRED FOR THE FENCE
 WALL AT THE GENERATOR AREA AS SHOWN ON SHEET S-13. THE
 HEIGHT OF THE WALL IS SPECIFIED AS 15', HOWEVER THE
 SITE PLANS SPECIFY 6'. PLEASE CORRECT. THE TAG FOR THE
 ELEVATION SHOULD REFERENCE 7 ON A1.2.3.
  
 13)ON THE COVERED WALKWAY PLAN ON S13, SPECIFY THE
 COLUMN TYPE AND REINFORCING FOR THE L ANGLE COLUMN
 BETWEEN SPANDREL PANELS 73 AND 74.ALSO SPECIFY THE
 FOUNDATION TYPE AND REINFORCEMENT FOR THE LARGE L ANGLE
 FOOTING AT THIS LOCATION.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE ROOF OF THE
 COVERED WALKWAY.
  
 15) THE SECTION OF EXTERIOR WALL ON THE EAST ELEVATION
 THAT IS LESS THAN 10 FEET FROM THE CONDO PROPERTY LINE
 (FIRE SEPARATION DISTANCE) IS REQUIRED BY FBC TABLE 602
 TO HAVE A ONE HOUR FIRE RATING FOR TYPE II-B
 CONSTRUCTION. IN ADDITION, FBC TABLE 704.8 LIMITS THE
 ALLOWABLE AREA OF UNPROTECTED OPENINGS TO 10% OF THE
 WALL AREA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714