Date |
Text |
2006-08-07 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| COMMENTS FROM FIRST REVIEW: |
| |
| 1. SHT A003 PLUMBING FIXTURE CALCULATION |
| INDICATE 3 DRINKING FOUNTAINS ARE |
| REQUIRED ON EACH FLOOR. CALCULATIONS |
| ALSO INDICATE THAT 4 DRINKING FOUNTAINS |
| ARE PROVIDED ON EACH FLOOR. A HIGH/LOW |
| DRINKING FOUNTAIN WITH ONE WASTE AND ONE |
| WATER SUPPLY IS CONSIDERED ONE FIXTURE. |
| ONLY 2 DRINKING FOUNTAINS ARE PROVIDED |
| ON EACH FLOOR, AND ONE MORE DRINKING |
| FOUNTAIN IS REQUIRED ON EACH FLOOR. |
| TABLE 403.1. |
| ****RESPONSE FROM ARCHITECT, PLEASE SEE |
| RESPONSE FROM ENGINEER. RESPONSE FROM |
| ENGINEER, SEE ARCHITECTS RESPONSE. |
| COMMENT NOT ADDRESSED. |
| |
| 2. SHT A105 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| SQUARE FOOTAGE FOR EACH AREA BEING |
| DRAINED ALONG WITH 1/2 THE AREA OF ALL |
| VERTICAL WALLS INCLUDING PARAPETS AS |
| WELL AS THE AREA OF ANY ROOFS THAT DRAIN |
| ONTO THE ROOF FROM ABOVE. SECTIONS 1106 |
| & 1107 AND ALL SUBSECTIONS. - SHOW THE |
| LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| OVERFLOW SCUPPERS. OVERFLOW SCUPPERS |
| SHALL BE SIZED PER SECTIONS 1101.7, |
| 1107.3 AND TABLE 1106.7. SCUPPER SIZE |
| CAN NOT BE CALCULATED WITHOUT REFERENCE |
| TO DEFLECTION OF THE ROOF. PLEASE SHOW |
| ON PLANS. |
| ****RESPONSE FROM ARCHITECT, PLEASE SEE |
| RESPONSE FROM ENGINEER. RESPONSE FROM |
| ENGINEER, SEE ARCHITECTS RESPONSE. |
| COMMENT NOT ADDRESSED. |
| |
| 3. SHT A402 SHOW THE CLEAR FLOOR SPACE |
| FOR ALL ACCESSIBLE FIXTURES INCLUDING |
| DRINKING FOUNTANS & UNINALS. SECTIONS |
| 11-4.15.5(1) AND 11-4.18.3. |
| ****RESPONSE NOTED, BUT CLEAR FLOOR |
| SPACE FOR THE DRINKING FOUNTAINS SHALL |
| BE FORWARD APPROACH. SECTION |
| 11-4.15.5(1). |
| |
| 4. OK |
| 5. OK |
| |
| 6. SHT P5.1 SANITARY RISER RISER |
| ISOMETRIC. SHOW ALL PIPE SIZES AND |
| INDICATE DFU'S AS THEY ACCUMULATE IN THE |
| SYSTEM. SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT SOME PIPE SIZES |
| ARE STILL MISSING, AND DFU'S NEED TO BE RECHECKED. |
| |
| 7. AN RPZV BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE TO THE BUILDING. SECTION |
| 608.13.2 AND CROSS CONNECTION MANUAL |
| SECTION 2.6. |
| ****RESPONSE NOTED, BUT SHT P3.1 REFERS |
| TO SHT P4.2 WHICH REFERS TO THE CIVIL |
| PLANS. CIVIL DOES NOT SHOW THE METER OR |
| BACKFLOW LOCATION. PLEASE INDICATE THE |
| LOCATION OF METER & RPBV BACKFLOW |
| REQUIRED ON THE WATER SERVICE. SECTION |
| 106.1.1. |
| |
| 8. OK |
| 9. OK |
| |
| 10. SUBMIT THE MANUF. SPECIFICATION |
| SHEET FOR THE PUMPS. PUMPS SHALL BE |
| LISTED. INDICATE MODEL NUMBER FOR EACH |
| PUMP. SECTION 303.4. |
| ****RESPONSE NOTED, BUT LISTING FOR |
| PUMPS ARE NOT SHOWN ON SHT P8.2. |
| |
| 11. SHT P7.1 CISTERN WATER RISER. MORE |
| INFORMATION IS REQUIRED. INDICATE |
| BUILDING SHOWN ON THE RISERS. SHOW ALL |
| PIPE SIZES, AND SHOW THE LOCATIONS FOR |
| THE REQUIRED BACKFLOWS WHERE THE POTABLE |
| WATER TIES INTO THE NON-POTABLE WATER. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT THE BUILDING |
| INDICATION IS NOT SHOWN, AND THE |
| REQUIRED BACKFLOW IS NOT SHOWN. |
| |
| 12. OK |
| |
| **************NEW COMMENTS************** |
| |
| 1B. SHT 0000 (BOTH), INDEX OF DRAWINGS |
| DOES NOT REFLECT SHEETS SUBMITTED. SOME |
| SHEETS HAVE NOT BEEN SUBMITTED, SOME |
| SHEETS SUBMITTED, BUT ARE NOT INDICATED |
| ON THE INDEX, AND SOME SHEETS ARE |
| MISNUMBERED. PLEASE CORRELATE INDEX AND |
| SHEETS FOR PLANS. SECTION 106.1.1. |
| |
| 2B. SHT P0.1 PLUMBING SHEET INDEX SHOWS |
| SHT P1.1. THIS SHEET HAS NOT BEEN |
| SUBMITTED. CORRELATE INDEX AND SHEETS. |
| SECTION 106.1.1. |
| |
| 3B. SHT P5.1 FITTINGS SHALL BE INSTALLED |
| TO GUIDE SEWAGE AND WASTE IN THE |
| DIRECTION OF FLOW. SECTION 706.3. THE |
| DOUBLE LAV SHOWN ON RISER SHOWS FITTING |
| AGAINST THE FLOW. PLEASE CORRECT. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561)805-6731 |
| E-MAIL [email protected] |