2006-08-09 00:00:00PROVISO:
 RESPONSE TO COMMENTS FROM REVIEW DATED,
 2-17-06 ARE ACCEPTABLE FOR COMMENTS 1
 THROUGH 4.
  
 COMMENT 5: FLOOR DRAINS IN MECHANICAL
 ROOMS - MECHANICAL ROOMS ARE USED AS
 RETURN AIR PLENUMS AND SHALL COMPLY WITH
 THE FOLLOWING:
 A) 2004 FPC 901.2
 B) ASHRAE 62-01 SECTION 8.4.1.11
 C) 2004 FMC 603.9
  
 COMMENT 6: CONDENSER WATER PIPING WILL
 BE SCHEDULE 40 BLACK STEAL.PLEASE
 INDICATE IF THIS WILL BE WELDED,
 GROOVED, THREADED, ETC.
  
 NEW COMMENT:
 COMMENT 7:PLEASE NOTE, PLAN SHEET M0.1
 ON THE MECHANICAL SHEET INDEX INDICATES
 SHEET M8.1. THIS PLAN WAS NOT SUBMITTED
 FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6179.