Plan Review Notes For Permit 05121217 |
Permit Number |
05121217 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-08-09 00:00:00 | PROVISO: | | RESPONSE TO COMMENTS FROM REVIEW DATED, | | 2-17-06 ARE ACCEPTABLE FOR COMMENTS 1 | | THROUGH 4. | | | | COMMENT 5: FLOOR DRAINS IN MECHANICAL | | ROOMS - MECHANICAL ROOMS ARE USED AS | | RETURN AIR PLENUMS AND SHALL COMPLY WITH | | THE FOLLOWING: | | A) 2004 FPC 901.2 | | B) ASHRAE 62-01 SECTION 8.4.1.11 | | C) 2004 FMC 603.9 | | | | COMMENT 6: CONDENSER WATER PIPING WILL | | BE SCHEDULE 40 BLACK STEAL.PLEASE | | INDICATE IF THIS WILL BE WELDED, | | GROOVED, THREADED, ETC. | | | | NEW COMMENT: | | COMMENT 7:PLEASE NOTE, PLAN SHEET M0.1 | | ON THE MECHANICAL SHEET INDEX INDICATES | | SHEET M8.1. THIS PLAN WAS NOT SUBMITTED | | FOR REVIEW. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6179. |
|