Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-11 00:00:00DENIED BY BUILDING
  
 2004 FLORIDA BUILDING CODE
 4 STORY OFFICE BUILDING (SHELL)
 TYPE II-B (SPRINKLERED)
 BUSINESS OCCUPANCY
 FLOOD ZONE A9 BFE 13' (+6" CITY REQ)
 REQUIRED SOIL BEARING CAPACITY 2500 AND
 8000 PSF
  
 1) STRUCTURE IS LOCATED IN AN A9 FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT A SIGNED AND SEALED SURVEY OR
 SITE PLAN INDICATING THE LOCATION OF THE
 STRUCTURE AND THE DISTANCE TO THE
 PROPERTY LINES (CONDO BOUNDARY LINES).
 THIS IS REQUIRED TO DETERMINE THE FIRE
 SEPARATION DISTANCE, AS WELL AS,
 EXTERIOR WALL FIRE RATINGS AND OPENING RESTRICTIONS.
  
 3) FBC* 1804.2.2 AREA OF QUESTIONABLE
 SOIL. SUBMIT A GEOTECHNICAL REPORT TO
 VERIFY THE SAFE BEARING CAPACITY OF THE
 SOIL.
  
 4) FBC 13-400.2.A.2 SHELL BUILDINGS.
 SHELL BUILDINGS SHALL COMPLY WITH THIS
 CODE BY METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED
 DESIGN PARAMETERS ARE
 KNOWN, A METHOD A CALCULATION MAY BE
 RESUBMITTED.
 13-400.3.ABC.2 CODE COMPLIANCE
 CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S
 ARCHITECT, OR OTHER AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY TO THE BUILDING OFFICIAL THAT
 THE BUILDING IS IN COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THIS CODE
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
 IF, DURING THE BUILDING?S CONSTRUCTION
 OR RENOVATION, ALTERATIONS ARE MADE IN
 THE BUILDING?S DESIGN OR IN MATERIALS OR
 EQUIPMENT INSTALLED IN THE BUILDING
 WHICH WOULD DIMINISH IT?S ENERGY
 PERFORMANCE, AN AMENDED COPY OF THE
 COMPLIANCE CERTIFICATION SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL ON OR
 BEFORE THE DATE OF FINAL INSPECTION BY
 THE BUILDING OWNER OR HIS OR HER LEGALLY AUTHORIZED
 AGENT.
 THE CERTIFIED FLA/COM CALCULATION
 PRINTOUT OR FORM 400C SHALL BE A PART OF
 THE PLANS AND SPECIFICATIONS SUBMITTED
 FOR PERMITTING.
 THE PARTY RESPONSIBLE UNDER SUBSECTIONS
 471.003 AND 481.228 AND CHAPTER 489,
 FLORIDA STATUTES , FOR THE DESIGN AND SPECIFICATION OF
 EACH BUILDING SYSTEM
 SHALL CERTIFY THAT THE PLANS AND
 SPECIFICATIONS FOR THAT SYSTEM COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF
 THIS CODE (SEE ALSO SECTION 13-103.2 ).
 PLEASE SUBMIT THE APPROPRIATE FORMS
 SIGNED AND SEALED BY THE DOR FOR EACH
 SYSTEM. ALSO SEE SECTION 13-101.1.6.
  
 5) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING PURPOSES
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, THRESHOLD INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 6) SEVERAL OF THE SECTION TAGS ARE
 INCORRECT ON SHEET S-5.
 - THERE IS A TAG FOR SECTION 11 ON S-10,
 BUT 11 ON S-10 IS BLANK.
 - THERE IS A TAG FOR SECTION 7 ON S-10,
 BUT 7 ON S-10 SAYS NOT USED.
 - TWO OF THE SECTION 9 ON S-10 TAGS ARE
 NOT IN THE CORRECT LOCATIONS ON S-5.
  
 7) THE WIND PRESSURES FOR THE WINDOW
 SCHEDULE ON SHEET A8.1.1 DO NOT CONCUR
 WITH THE OPENING PRESSURES ON S11.
  
 8) THE RAMP HEIGHT ON DRAWING 2 ON
 A1.2.1 IS 16" AND THE HEIGHT OF THE
 STEPS IS 18". PLEASE CORRECT.
  
 9) FBC 11-4.8.4 REQUIRES 72 INCHES OF
 STRAIGHT AND LEVEL CLEARANCE AT THE
 BOTTOM OF RAMPS. DRAWING 2 ON A1.2.1 HAS
 ONLY 60 INCHES OF CLEARANCE. PLEASE
 CORRECT.
  
 10) FBC 3002.4 ELEVATOR CAR TO
 ACCOMMODATE AMBULANCE STRETCHER.
 IN BUILDINGS FOUR STORIES IN HEIGHT OR
 MORE, AT LEAST ONE ELEVATOR SHALL BE
 PROVIDED FOR FIRE DEPARTMENT EMERGENCY
 ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR
 SHALL BE OF SUCH A SIZE AND ARRANGEMENT
 TO ACCOMMODATE A 24-INCH BY 76-INCH (610
 MM BY 1930 MM) AMBULANCE STRETCHER IN
 THE HORIZONTAL, OPEN POSITION AND SHALL
 BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE). THE SYMBOL SHALL NOT BE
 LESS THAN 3 INCHES (76 MM) HIGH AND
 SHALL BE PLACED INSIDE ON BOTH SIDES OF
 THE HOISTWAY DOOR FRAME. PROVIDE NOTE ON
 PLAN SPECIFYING THIS AND WHICH ELEVATOR
 COMPLIES.
  
 11) ELEVATORS SHALL COMPLY WITH
 ACCESSIBILITY REQUIRES OF FBC 3007 AND
 11-4.10. PROVIDE NOTE ON PLAN SPECIFYING
 SIGNAGE AND HEIGHT.
  
 12) SHOW THE CURB RAMPS REQUIRED BY FBC
 11-4.7 FROM THE ACCESSIBLE PARKING
 SPACES TO THE ACCESSIBLE SIDEWALK ON THE
 PLANS.
  
 13)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVAL COVERSHEETS WITH THE
 STATE FL # FOR ALL ITEMS REQUIRED BY
 RULE 9B-72. THIS IS REQUIRED IN ADDITION
 TO THE NOA OR OTHER EVALUATION
 REPORT/INSTALLATION INSTRUCTIONS.
  
 14) FBC*109.3.6 REQUIRES ALL PRODUCT
 APPROVALS SUBMITTED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:
 - STEEL DOOR TO THE ROOF (RO1)
 - FIRE CORRIDOR EXIT DOOR (107)
  
 16)TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 17) ALSO SEE HANDWRITTEN NOTES AND
 CORRECTIONS ON THE PLANS (SET #3).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved