Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A003 PLUMBING FIXTURE CALCULATION
 INDICATE 3 DRINKING FOUNTAINS ARE
 REQUIRED ON EACH FLOOR. CALCULATIONS
 ALSO INDICATE THAT 4 DRINKING FOUNTAINS
 ARE PROVIDED ON EACH FLOOR. A HIGH/LOW
 DRINKING FOUNTAIN WITH ONE WASTE AND ONE
 WATER SUPPLY IS CONSIDERED ONE FIXTURE.
 ONLY 2 DRINKING FOUNTAINS ARE PROVIDED
 ON EACH FLOOR, AND ONE MORE DRINKING
 FOUNTAIN IS REQUIRED ON EACH FLOOR.
 TABLE 403.1.
 2. SHT A105 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE FOR EACH AREA BEING
 DRAINED ALONG WITH 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS AS
 WELL AS THE AREA OF ANY ROOFS THAT DRAIN
 ONTO THE ROOF FROM ABOVE. SECTIONS 1106
 & 1107 AND ALL SUBSECTIONS. - SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS OR
 OVERFLOW SCUPPERS. OVERFLOW SCUPPERS
 SHALL BE SIZED PER SECTIONS 1101.7,
 1107.3 AND TABLE 1106.7. SCUPPER SIZE
 CAN NOT BE CALCULATED WITHOUT REFERENCE
 TO DEFLECTION OF THE ROOF. PLEASE SHOW
 ON PLANS.
 3. SHT A402 SHOW THE CLEAR FLOOR SPACE
 FOR ALL ACCESSIBLE FIXTURES INCLUDING
 DRINKING FOUNTANS & UNINALS. SECTIONS
 11-4.15.5(1) AND 11-4.18.3.
 4. SHT P0.1 PLUMBING NOTES #13: AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 FROM REFERENCE. SECTION 604.9. WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED NEAR THE FIXTURES
 IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 5. ALL NON-POTABLE WATER SYSTEMS AND
 PIPES SHALL BE LABELED. SECTION 608.8.
 6. SHT P5.1 SANITARY RISER RISER
 ISOMETRIC. SHOW ALL PIPE SIZES AND
 INDICATE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 106.1.1.
 7. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2 AND CROSS CONNECTION MANUAL
 SECTION 2.6.
 8. SHT P6.1 FULL OPEN VALVE REQUIRED AT
 THE BASE OF EVERY WATER RISER PIPE.
 SECTION 606.1(3).
 9. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR
 THE CONDENSATE AND THE STORM SYSTEMS.
 THIS SHALL INCLUDE THE VERTICAL RISERS
 AND THE BUILDING DRAINS. SHOW ALL PIPE
 SIZES FOR BOTH SYSTEMS, AND SHOW THE
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM FOR THE STORM SYSTEM. SECTION
 106.3.5.1.3.
 10. SUBMIT THE MANUF. SPECIFICATION
 SHEET FOR THE PUMPS. PUMPS SHALL BE
 LISTED. INDICATE MODEL NUMBER FOR EACH
 PUMP. SECTION 303.4.
 11. SHT P7.1 CISTERN WATER RISER. MORE
 INFORMATION IS REQUIRED. INDICATE
 BUILDING SHOWN ON THE RISERS. SHOW ALL
 PIPE SIZES, AND SHOW THE LOCATIONS FOR
 THE REQUIRED BACKFLOWS WHERE THE POTABLE
 WATER TIES INTO THE NON-POTABLE WATER.
 SECTION 106.1.1.
 12. SHOW THE SIZE OF ALL DOWNSPOUTS ON
 THE STORM DRAINAGE SYSTEM. IF COLLECTOR
 HEADS FOR THE PRIMARY ROOF DRAINS.
 SUBMIT A DETAIL SHOWING SIZE, HEIGHT &
 WIDTH. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  