2006-03-11 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A003 PLUMBING FIXTURE CALCULATION |
| INDICATE 3 DRINKING FOUNTAINS ARE |
| REQUIRED ON EACH FLOOR. CALCULATIONS |
| ALSO INDICATE THAT 4 DRINKING FOUNTAINS |
| ARE PROVIDED ON EACH FLOOR. A HIGH/LOW |
| DRINKING FOUNTAIN WITH ONE WASTE AND ONE |
| WATER SUPPLY IS CONSIDERED ONE FIXTURE. |
| ONLY 2 DRINKING FOUNTAINS ARE PROVIDED |
| ON EACH FLOOR, AND ONE MORE DRINKING |
| FOUNTAIN IS REQUIRED ON EACH FLOOR. |
| TABLE 403.1. |
| 2. SHT A105 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| SQUARE FOOTAGE FOR EACH AREA BEING |
| DRAINED ALONG WITH 1/2 THE AREA OF ALL |
| VERTICAL WALLS INCLUDING PARAPETS AS |
| WELL AS THE AREA OF ANY ROOFS THAT DRAIN |
| ONTO THE ROOF FROM ABOVE. SECTIONS 1106 |
| & 1107 AND ALL SUBSECTIONS. - SHOW THE |
| LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| OVERFLOW SCUPPERS. OVERFLOW SCUPPERS |
| SHALL BE SIZED PER SECTIONS 1101.7, |
| 1107.3 AND TABLE 1106.7. SCUPPER SIZE |
| CAN NOT BE CALCULATED WITHOUT REFERENCE |
| TO DEFLECTION OF THE ROOF. PLEASE SHOW |
| ON PLANS. |
| 3. SHT A402 SHOW THE CLEAR FLOOR SPACE |
| FOR ALL ACCESSIBLE FIXTURES INCLUDING |
| DRINKING FOUNTANS & UNINALS. SECTIONS |
| 11-4.15.5(1) AND 11-4.18.3. |
| 4. SHT P0.1 PLUMBING NOTES #13: AIR |
| CHAMBERS ARE NOT APPROVED. PLEASE DELETE |
| FROM REFERENCE. SECTION 604.9. WATER |
| HAMMER ARRESTORS REQUIRED BY SECTION |
| 604.9 SHALL BE LOCATED NEAR THE FIXTURES |
| IN AN "EFFECTIVE RANGE" NOT IN THE |
| CEILING. PDI-WH 201 AND MANUF. |
| INSTALLATION INSTRUCTIONS. |
| 5. ALL NON-POTABLE WATER SYSTEMS AND |
| PIPES SHALL BE LABELED. SECTION 608.8. |
| 6. SHT P5.1 SANITARY RISER RISER |
| ISOMETRIC. SHOW ALL PIPE SIZES AND |
| INDICATE DFU'S AS THEY ACCUMULATE IN THE |
| SYSTEM. SECTION 106.1.1. |
| 7. AN RPZV BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE TO THE BUILDING. SECTION |
| 608.13.2 AND CROSS CONNECTION MANUAL |
| SECTION 2.6. |
| 8. SHT P6.1 FULL OPEN VALVE REQUIRED AT |
| THE BASE OF EVERY WATER RISER PIPE. |
| SECTION 606.1(3). |
| 9. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR |
| THE CONDENSATE AND THE STORM SYSTEMS. |
| THIS SHALL INCLUDE THE VERTICAL RISERS |
| AND THE BUILDING DRAINS. SHOW ALL PIPE |
| SIZES FOR BOTH SYSTEMS, AND SHOW THE |
| SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| SYSTEM FOR THE STORM SYSTEM. SECTION |
| 106.3.5.1.3. |
| 10. SUBMIT THE MANUF. SPECIFICATION |
| SHEET FOR THE PUMPS. PUMPS SHALL BE |
| LISTED. INDICATE MODEL NUMBER FOR EACH |
| PUMP. SECTION 303.4. |
| 11. SHT P7.1 CISTERN WATER RISER. MORE |
| INFORMATION IS REQUIRED. INDICATE |
| BUILDING SHOWN ON THE RISERS. SHOW ALL |
| PIPE SIZES, AND SHOW THE LOCATIONS FOR |
| THE REQUIRED BACKFLOWS WHERE THE POTABLE |
| WATER TIES INTO THE NON-POTABLE WATER. |
| SECTION 106.1.1. |
| 12. SHOW THE SIZE OF ALL DOWNSPOUTS ON |
| THE STORM DRAINAGE SYSTEM. IF COLLECTOR |
| HEADS FOR THE PRIMARY ROOF DRAINS. |
| SUBMIT A DETAIL SHOWING SIZE, HEIGHT & |
| WIDTH. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |