2006-02-17 00:00:00DENIED:
 1.PLAN SHEET M.01 MECHANICAL NOTE #1,
 REFERENCE STANDARDS ARE NOT THE CURRENT
 STANDARDS AS ADOPTED WITH THE 2004 FBC.
 (EXAMPLE - ASHRAE 62-01, 15-01, 34-01,
 NFPA 90A-02, 90B-02, ETC).PLEASE
 VERIFY ALL REFERENCED STANDARDS.
  
 2.PLAN SHEET M0.2 O.A. CALCS & EXHAUST
 CALCS. REFERENCE THE WRONG ASHRAE
 STANDARD.
  
 3.PLAN SHEET M2.1.1, PLEASE INDICATE
 RETURN AIR.PLEASE NOTE, NO
 COMBUSTIBLES ALLOWED IN THE PLENUM PER
 2004 FMC 602.2.1
  
 4.PLAN SHEET M2.1.1, NOTES REFERENCE
 PLAN SHEET M7.3 FOR DETAIL OF THE
 UNDERFLOOR AIR HIGHWAY LOOP & THE FUTURE
 "YORK FLEXSYS VAV MIT TERMINAL
 DIFFUSER".DETAILS ON PLAN SHEET M7.3
 DO NOT SHOW THIS APPLICATION.ALL
 DETAILS INDICATE DUCT SYSTEM IN THE
 CEILING.PLEASE INDICATE HOW THE DUCT
 WILL BE SUPPORTED UNDER THE FLOOR.
  
 5.PLAN SHEET M2.1.1, 2.1.2, & 2.2.2
 MECHANICAL ROOMS ARE OPEN RETURN WITH
 FLOOR DRAINS INDICATED IN THE MECHANICAL
 ROOM.PLANS DO NOT PROVIDE A LAYOUT OF
 THE CONDENSATE FROM THE AHU.IS THE
 INTENT TO TERMINATE INTO THE FLOOR
 DRAIN? WHAT WILL BE THE PRESSURE
 DIFFERENTAL IN THE RETURN AIR PLENUM.
 PLEASE REFERENCE 2004 FPC SECTION 901.2.
  
 6.PLEASE INDICATE PIPING MATERIAL FOR
 THE CONDENSER WATER.2004 FMC CHAPTER
 12.
  