2006-02-09 00:00:00DENIED:
  
 1) SHALL COMPLY NFPA 101 LIFE SAFETY
 CODE 2003 EDITION AND NFPA 1 UNIFORM
 FIRE CODE 2003 EDITION.
  
 2) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION
 SERVICE.
  
 3) SINCE TENANT SPACE IS FUTURE THE FIRE
 ALARM DEVICES FOR THOSE TENANT SPACE
 MUST BE COMPARIBLE TO THE ORIGINAL FIRE
 ALARM SYSTEM AND UL CERTIFY.
  
 4) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 5) SEPARATE SHOP DRAWING AND PERMIT
 APPLICATION ARE REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM.
  
 6) PLEASE SEE NFPA 101 2003 EDITION
 CHAPTER 7.7.2 DISCHARGE THROUGH AREAS ON
 LEVEL EXIT DISCHARGE. NOT MORE THAN 50%
 OF THE REQUIRED NUMBER OF EXITS, AND NOT
 MORE THAN 50% OF THE REQUIRED EGRESS
 CAPACITY, SHALL BE PERMITTED TO
 DISCHARGE THROUGH AREAS ON THE LEVEL OF
 EXIT DISCHARGE, UNLESS OTHERWISE
 PERMITTED IN 7.7.2.1 AND 7.7.2.2,
 PROVIDED THAT THE CRITERIA OF 7.7.2.3
 THROUGH 7.7.2.7 ARE MET.
  
 7) INTERIOR WALL AND CEILING FINISH
 MATERIAL COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A OR CLASS B IN EXITS,
 EXIT ACCESS CORRIDORS, AND CLASS A,
 CLASS B, OR CLASS C IN ALL OTHER AREAS.
  
 8) PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED IN EVERY BUSINESS OCCUPANCY IN
 ACCORDANCE WITH 9.7.4.1.
  
  