Date |
Text |
2006-02-10 00:00:00 | IN ELEC FOR REVIEW. |
| ********** UNSAT ********** |
| |
| ** PLEASE KNOW, PLANS AND SUBMITTIALS |
| ARE NOT COMPLETE AT THIS TIME. |
| |
| |
| 1)NOTE: PLEASE SEE ALL CURRENT CODES |
| SHALL BE REFERENCED TO THE CURRENT CODES |
| IN EFFECT. PLEASE SEE PLANS CALL FOR |
| 2001 FLORIDA BUILDING CODE. PLEASE KNOW, |
| AS OF OCT 1ST, 2005 THE NEW FBC IS THE |
| 2004 EDITION. PLEASE SEE THE FOLLOWING |
| SHALL BE REFERENCED. 2003 NFPA-101, 2002 |
| NFPA-70, AND 2002 NFPA-72 |
| |
| 2)NOTE: PLANS WILL REQUIRED BATTERY BACK |
| UP LT FIXTURES IN MAIN ELECTRICAL RM, |
| ELEVATOR RMS. |
| PLEASE ALSO KNOW BATTERY BACK UP |
| FIXTURES WILL BE REQUIRED IN STAIRWAY |
| AND EGRESS PATHS TO PROVIDE A MIN OF 1FT |
| CANDLE OF LIGHT BY SOME SORT OF BATTEY |
| BACK UP FIXTURE. PLEASE SEE NFPA-101 |
| 7.9.2.2, TRIPPING OR SHUTTING OFF ANY |
| SINGLE DEVICE OR MEANS OF OVERCURRENT |
| PROTECTION SHALL NOT LEAVE ANY ONE |
| EGRESS PATH IN TOTAL DARKNESS. |
| PLEASE PROVIDE PHOTOMETRICS FOR |
| STAIRWAYS, AS THE 2003 LS 101 7.8.1.3 |
| REQUIRES A MIN OF 10FT CANDLES(108LUX) |
| IN STAIRWAYS UNDER NORMAL LIGHTING |
| CONDITIONS AND 7.9.2.2 PERMITS THE |
| DERATING TO A MIN OF 1FT CANDLE UNDER |
| EMERGENCY CONDITIONS. |
| 700.16.,700.12E ETC |
| |
| 3)NOTE: PLEASE SEE ADDRESS REVIEW. |
| PLEASE KNOW, IF PROPERTY CHANGE LEGALLY |
| TO SEPARATE PROPERTIES/ PCN. ELECTRICAL |
| DESIGN MAY BE AFFECTED. PLEASE ALSO |
| KNOW, LEGAL EASEMENTS MAY BE REQUIED. |
| |
| 4)NOTE: PLEASE SEE REQUIREMENTS OF |
| 225.31-225.39 FOR FEEDERS COMING FROM |
| GARAGE BLDG. |
| PLEASE SEE MEAANS OF DISCONNECT FOR ALL |
| FEEDERS FROM GARAGE IS REQUIRED, ALL |
| MUST BE GROUPED AND RATED FOR THE LOAD |
| SERVED , IN CLUDING ALL AS NOTED IN |
| ABOVE CODES. |
| PLEASE SEE ELECTRICAL RISER WILL BE |
| AFFECTED WITH CHANGES AND A MORE |
| COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| BE DONE THAT TIME. |
| |
| 5)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| ELECTRODE SYSTEMS AT SEPARATE BLDGS. |
| PLEASE ALSO PROVIDE A ONE-LINE DIAGRAM |
| OF THE ENTIRE GROUNDING ELECTRODE |
| CONDUCTOR AND GROUNDING ELECTRODE SYSTEM |
| PER 250.58,250.30 |
| |
| 6)NOTE: PLEASE PROVIDE WIND LOAD |
| CALCUALTIONS FOR BLDG REVIEW FOR ANY |
| SITE LIGHTING POLES BEING RELOCATED OR |
| NEW. ALL MUST MEET 2004 FBC 140 MPH |
| |
| 7)NOTE: PLEASE SEE E-1.2 WHICH SHOWS A |
| PANEL HP AND DISCONNECT, HOWEVER THESE |
| ARE NOT LOCATED ON RISER FOR REVIEW? |
| PLEASE ALSO SEE A NOTE #2 IS SHOWN ON |
| PLANS, HOWEVER A NOTE #2 IS NOT ON SHEET |
| FOR EXPLANATION OF NOTE?? |
| 215.5 |
| |
| 8)NOTE: PLEASE SEE 620.23,620.24 FOR |
| REQUIRED DEDICATED CIRCUITS IN ALL |
| ELEVATOR EQUIPMENT RMS. PLEASE ALSO SEE |
| ELEVATOR PITS, LTS, GFI ARE ALSO |
| REQUIRED TO BE DEDICATED. |
| |
| 9)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125% 215.3,230.42 ETC |
| |
| 10)NOTE: PLEASE PLACE NOTE ON "LIGHTNING |
| PROTECTION PLANS". ANY PROPOSED |
| LIGHTNING PROTECTION SYSTEM SHALL MEET |
| NFPA-780. OR WORDS TO THAT AFFECT. |
| IT WAS NOTED THE LIGHTNING PROTECTION |
| WILL BE UNDER A SEPARATE PERMIT. |
| |
| 11)NOTE: PLEASE SEE ALL PANELS ON THE |
| LOAD SIDE OF TRANSFORMERS SHALL CONTAIN |
| MCB'S AS REQUIRED PER 408.16 |
| |
| 12)NOTE: PLEASE SEE RISER AS SHOWN UNDER |
| THIS PERMIT SHALL BE COMPLETE WITH ALL |
| FEEDERS, CONDUITS ETC. |
| 215.5 |
| |
| 14)NOTE: PLEASE INDICATE ALL PANELS WITH |
| FEED-THRU LUGS FROMTHE SECONDARY SIDE OF |
| |
| L1A, L2A, L3A ETC |
| 215.5 |
| |
| 15)NOTE: PLEASE COMPLETE AND SUBMIT MIN |
| LOAD CALCUALTIONS AS REQUIRED PER |
| NEC.220 |
| |
| 16)NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP |
| INFORMATION NEEDED. |
| |
| 17)NOTE: PLEASE SEE LIGHTING |
| REQUIREMENTS UNDER 13-415 FOR AREAS OF |
| CONTROL AND TANDEM WIRING. |
| PLEASE SPECIFY THIS INFORMATION ON |
| PLANS. |
| |
| 18)NOTE: PLEASE SEE MANY OF THE |
| ENGINEER'S SEALS ARE NOT |
| "RAISED/EMBOSSED" ENOUGH TO CLEARLY SHOW |
| ALL INFORMATION AS REQUIRED UNDER FS |
| 471.025 |
| PLEASE KNOW, ALL SEALS MUST CONTAIN THE |
| WORD "LICENSE" INSTEAD OF THE OLD |
| "CERTIFICATE", IF SEAL IS NEWER AND |
| MENTIONS "LICENSE PLEASE DISREGARD. |
| PLEASE SEE THE FBPE'S HAD EXTENDED THE |
| DATE TO JAN 1ST,2006 FOR ALL SEALS TO BE |
| CHANGED. |
| |
| 19)NOTE: PLEASE SEE LANDSCAPE PLANS ARE |
| SEALED "PHOTO-COPIES" OF ARCHITECT'S |
| SIGNATURE. PLEASE SEE FS 481.221 WHICH |
| REQUIRES THE SIGNATURE TO BE AN ORIGINAL |
| SIGNATURE. |
| |
| ** PLEASE KNOW, REVIEW FOR MAIN BLDG HAS |
| NOT COMMENCED AT THIS TIME. |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ON.Y INSERT NEW REVISED SHEETS INTO |
| COMPLETED SETS FOR REVIEW AND STAMPING. |
| ONLY SUBMIT ONE COPY OF OLD/VOIDED |
| SHEETS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| DPALMER2WPB.ORG |
| |
| |