Plan Review Notes
Plan Review Notes For Permit 05121217
Permit Number 05121217
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-10 00:00:00IN ELEC FOR REVIEW.
 ********** UNSAT **********
  
 ** PLEASE KNOW, PLANS AND SUBMITTIALS
 ARE NOT COMPLETE AT THIS TIME.
  
  
 1)NOTE: PLEASE SEE ALL CURRENT CODES
 SHALL BE REFERENCED TO THE CURRENT CODES
 IN EFFECT. PLEASE SEE PLANS CALL FOR
 2001 FLORIDA BUILDING CODE. PLEASE KNOW,
 AS OF OCT 1ST, 2005 THE NEW FBC IS THE
 2004 EDITION. PLEASE SEE THE FOLLOWING
 SHALL BE REFERENCED. 2003 NFPA-101, 2002
 NFPA-70, AND 2002 NFPA-72
  
 2)NOTE: PLANS WILL REQUIRED BATTERY BACK
 UP LT FIXTURES IN MAIN ELECTRICAL RM,
 ELEVATOR RMS.
 PLEASE ALSO KNOW BATTERY BACK UP
 FIXTURES WILL BE REQUIRED IN STAIRWAY
 AND EGRESS PATHS TO PROVIDE A MIN OF 1FT
 CANDLE OF LIGHT BY SOME SORT OF BATTEY
 BACK UP FIXTURE. PLEASE SEE NFPA-101
 7.9.2.2, TRIPPING OR SHUTTING OFF ANY
 SINGLE DEVICE OR MEANS OF OVERCURRENT
 PROTECTION SHALL NOT LEAVE ANY ONE
 EGRESS PATH IN TOTAL DARKNESS.
 PLEASE PROVIDE PHOTOMETRICS FOR
 STAIRWAYS, AS THE 2003 LS 101 7.8.1.3
 REQUIRES A MIN OF 10FT CANDLES(108LUX)
 IN STAIRWAYS UNDER NORMAL LIGHTING
 CONDITIONS AND 7.9.2.2 PERMITS THE
 DERATING TO A MIN OF 1FT CANDLE UNDER
 EMERGENCY CONDITIONS.
 700.16.,700.12E ETC
  
 3)NOTE: PLEASE SEE ADDRESS REVIEW.
 PLEASE KNOW, IF PROPERTY CHANGE LEGALLY
 TO SEPARATE PROPERTIES/ PCN. ELECTRICAL
 DESIGN MAY BE AFFECTED. PLEASE ALSO
 KNOW, LEGAL EASEMENTS MAY BE REQUIED.
  
 4)NOTE: PLEASE SEE REQUIREMENTS OF
 225.31-225.39 FOR FEEDERS COMING FROM
 GARAGE BLDG.
 PLEASE SEE MEAANS OF DISCONNECT FOR ALL
 FEEDERS FROM GARAGE IS REQUIRED, ALL
 MUST BE GROUPED AND RATED FOR THE LOAD
 SERVED , IN CLUDING ALL AS NOTED IN
 ABOVE CODES.
 PLEASE SEE ELECTRICAL RISER WILL BE
 AFFECTED WITH CHANGES AND A MORE
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN
 BE DONE THAT TIME.
  
 5)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEMS AT SEPARATE BLDGS.
 PLEASE ALSO PROVIDE A ONE-LINE DIAGRAM
 OF THE ENTIRE GROUNDING ELECTRODE
 CONDUCTOR AND GROUNDING ELECTRODE SYSTEM
 PER 250.58,250.30
  
 6)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW FOR ANY
 SITE LIGHTING POLES BEING RELOCATED OR
 NEW. ALL MUST MEET 2004 FBC 140 MPH
  
 7)NOTE: PLEASE SEE E-1.2 WHICH SHOWS A
 PANEL HP AND DISCONNECT, HOWEVER THESE
 ARE NOT LOCATED ON RISER FOR REVIEW?
 PLEASE ALSO SEE A NOTE #2 IS SHOWN ON
 PLANS, HOWEVER A NOTE #2 IS NOT ON SHEET
 FOR EXPLANATION OF NOTE??
 215.5
  
 8)NOTE: PLEASE SEE 620.23,620.24 FOR
 REQUIRED DEDICATED CIRCUITS IN ALL
 ELEVATOR EQUIPMENT RMS. PLEASE ALSO SEE
 ELEVATOR PITS, LTS, GFI ARE ALSO
 REQUIRED TO BE DEDICATED.
  
 9)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% 215.3,230.42 ETC
  
 10)NOTE: PLEASE PLACE NOTE ON "LIGHTNING
 PROTECTION PLANS". ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL MEET
 NFPA-780. OR WORDS TO THAT AFFECT.
 IT WAS NOTED THE LIGHTNING PROTECTION
 WILL BE UNDER A SEPARATE PERMIT.
  
 11)NOTE: PLEASE SEE ALL PANELS ON THE
 LOAD SIDE OF TRANSFORMERS SHALL CONTAIN
 MCB'S AS REQUIRED PER 408.16
  
 12)NOTE: PLEASE SEE RISER AS SHOWN UNDER
 THIS PERMIT SHALL BE COMPLETE WITH ALL
 FEEDERS, CONDUITS ETC.
 215.5
  
 14)NOTE: PLEASE INDICATE ALL PANELS WITH
 FEED-THRU LUGS FROMTHE SECONDARY SIDE OF
  
 L1A, L2A, L3A ETC
 215.5
  
 15)NOTE: PLEASE COMPLETE AND SUBMIT MIN
 LOAD CALCUALTIONS AS REQUIRED PER
 NEC.220
  
 16)NOTE: PLEASE SEE FBC 2004 CHAPTER 13,
 13-413.1ABC.1.1, .2 FOR VOLTAGE DROP
 INFORMATION NEEDED.
  
 17)NOTE: PLEASE SEE LIGHTING
 REQUIREMENTS UNDER 13-415 FOR AREAS OF
 CONTROL AND TANDEM WIRING.
 PLEASE SPECIFY THIS INFORMATION ON
 PLANS.
  
 18)NOTE: PLEASE SEE MANY OF THE
 ENGINEER'S SEALS ARE NOT
 "RAISED/EMBOSSED" ENOUGH TO CLEARLY SHOW
 ALL INFORMATION AS REQUIRED UNDER FS
 471.025
 PLEASE KNOW, ALL SEALS MUST CONTAIN THE
 WORD "LICENSE" INSTEAD OF THE OLD
 "CERTIFICATE", IF SEAL IS NEWER AND
 MENTIONS "LICENSE PLEASE DISREGARD.
 PLEASE SEE THE FBPE'S HAD EXTENDED THE
 DATE TO JAN 1ST,2006 FOR ALL SEALS TO BE
 CHANGED.
  
 19)NOTE: PLEASE SEE LANDSCAPE PLANS ARE
 SEALED "PHOTO-COPIES" OF ARCHITECT'S
 SIGNATURE. PLEASE SEE FS 481.221 WHICH
 REQUIRES THE SIGNATURE TO BE AN ORIGINAL
 SIGNATURE.
  
 ** PLEASE KNOW, REVIEW FOR MAIN BLDG HAS
 NOT COMMENCED AT THIS TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ON.Y INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONLY SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  