2006-05-01 00:00:00 | DENIED BY BUILDING |
| |
| 1641 WORTHINGTON ROAD |
| 4 STORY OFFICE BUILDING (SHELL) |
| TYPE II-A (SPRINKLERED) |
| BUSINESS OCCUPANCY |
| FLOOD ZONE A9 BFE 13' (+6" CITY REQ) |
| REQUIRED SOIL BEARING CAPACITY 2500 AND |
| 8000 PSF |
| |
| 1) STRUCTURE IS LOCATED IN AN A9 FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 2) SUBMIT A SIGNED AND SEALED SURVEY OR |
| SITE PLAN INDICATING THE LOCATION OF THE |
| STRUCTURE AND THE DISTANCE TO THE |
| PROPERTY LINES THAT ARE SHOWN ON THE |
| SURVEY OF UNIT 7A. THIS IS REQUIRED TO |
| DETERMINE FIRE SEPARATION DISTANCE, AS |
| WELL AS, EXTERIOR WALL FIRE RATINGS, |
| ALLOWABLE AREA OF OPENINGS AND OPENING |
| PROTECTION REQUIREMENTS. SEE FBC 704.1. |
| |
| 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4) NOTE #3 ON S6 UNDER FOUNDATIONS |
| STATES THAT SOIL CAPABLE OF SUPPORTING |
| 8000 PSF AND 2500 PSF IS REQUIRED AND |
| REFERS TO PLAN FOR LOCATIONS. SPECIFY |
| THE LOCATIONS WHERE 8000 PSF SOIL |
| BEARING CAPACITY IS REQUIRED ON S1. |
| |
| 5) 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF |
| THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 6) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| STAMPED AT THAT OFFICE AND A COPY OF THE |
| PAID RECEIPT SUBMITTED TO THE CITY OF |
| WEST PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| |
| 7) FBC 13-101.1.6SHELL BUILDINGS. |
| THE WHOLE BUILDING (INCL. FUTURE TENANT |
| SPACE) SHALL BE CONSIDERED.SHELL |
| BUILDINGS SHALL BE SHOWN TO COMPLY WITH |
| METHOD B OR C.(SEE SUB-CHAPTER 4).ALL ASSUMPTIONS |
| MADE ABOUT SYSTEMS, NOT |
| SHOWN ON THE CURRENT PLANS, SHALL BE |
| LISTED AND APPENDED TO THE FORM 400B FOR SUBMITTAL. |
| THIS WILL BE COMPARED, AT A |
| LATER DATE, TO THE ACTUAL SYSTEMS |
| PROPOSED BY THE FUTURE TENANT(S).THE |
| ASSUMPTIONS LISTED ON THE APPENDIX SHEET |
| SHALL BE AT LEAST THE MINIMUM STANDARD |
| (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE |
| BUILDING TO BE OCCUPIED FOR IT'S |
| INTENDED PURPOSE. SUBMIT AN ACCURATELY |
| COMPLETED FORM 400B-04 DEMONSTARATING |
| THAT CODE COMPLIANCE HAS BEEN ACHIEVED. |
| THE ONE SUBMITTED INDICATES THE BUILDING |
| ENVELOPE FAILS. |
| |
| 8) FBC* 105.13.1SPECIAL INSPECTOR.A |
| STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED PRIOR TO THE ISSUANCE OF A |
| BUILDING PERMIT FOR THE CONSTRUCTION OF |
| A THRESHOLD BUILDING.A THRESHOLD |
| BUILDING IS ANY BUILDING WHICH IS |
| GREATER THAN THREE STORIES OR 50 FEET IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY |
| OCCUPANCY WITH 5,000 SQFT AREA AND |
| GREATER THAN 500 OCCUPANTS.THREE |
| COPIES OF THE PLANS AND OTHER DOCUMENTS |
| WILL BE REQUIRED FOR PERMITTING PURPOSES |
| ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| SERVICES MANAGER - TEL: |
| 561 805 6711), A MEETING INVOLVING THE |
| OWNER, THRESHOLD INSPECTOR, JOB |
| INSPECTOR, CONTRACTOR AND ENGINEER. |
| |
| 9)FBC* 109.3.6.4.4 ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED |
| AND SEALED BY THE ARCHITECT OR ENGINEER |
| OF RECORD CON- TAIN A STATEMENT THAT, TO |
| THE BEST OF THE ARCHITECT'S PR |
| ENGINEER'S KNOWLEDGE, THE PLANS AND |
| SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 10) PLEASE EXPLAIN THE +ACI-, +ADO-, |
| +AEA-, +AF-, ETC. IN THE NOTES ON SHEET |
| S-6. |
| |
| 11) SHEET S7 SPECIFIES 9-1/4" THICK TILT |
| WALL PANELS AT THE ELEVATOR SHAFTS, |
| HOWEVER, 8" THICK PANELS ARE INDICATED |
| AT THIS LOCATION ON SHEETS S1-S4. PLEASE |
| CLARIFY. |
| |
| 12) THE SECTION LINES FOR SECTION 9/S10 |
| ON SHEET S5 APPEAR TO BE IN THE WRONG |
| LOCATION OR ARE LABELED INCORRECTLY. |
| |
| 13) THE COMPONENT AND CLADDING WINDLOAD |
| PRESSURES ON SHEET S11 FOR THE FLAT ROOF |
| ARE INCORRECT. SEE FBC TABLE 1609.6B |
| (ROOF 0-10 DEGREES) AND TABLE 1609.6D |
| FOR THE BUILDING HEIGHT ADJUSTMENT |
| FACTOR. |
| |
| 14) THE WINDOW AND DOOR WINDLOAD |
| PRESSURES ON S11 ARE INCORRECT. SEE FBC |
| TABLE 1609B (WALL) AND TABLE 1609.6D FOR |
| THE HEIGHT ADJUSTMENT FACTOR. |
| |
| 15) THE CISTERNS ON A001 ARE REQUIRED TO |
| BE ANCHORED TO RESIST OVERTURNING PER |
| FBC 1609.1.3. |
| |
| 16) SHEET A003 INCORRECTLY LISTS FBC |
| TABLE 500 FOR ALLOWABLE HEIGHT AND |
| BUILDING AREA. THIS HAS BEEN CHANGED TO |
| TABLE 503 IN THE 2004 FBC. |
| |
| 17) ON SHEET A003 UNDER HURRICANE |
| CRITERIA THE CORRECT EDITION OF ASCE 7 |
| IS ASCE 7-02. |
| |
| 18) SPECIFY THE FIRE PROTECTION AND FIRE |
| RATINGS FOR ALL STRUCTURAL MEMBERS |
| (STEEL COLUMNS, BEAMS, BAR JOISTS, ETC.) |
| SEE FBC 714.2. |
| |
| 19) SPECIFY THE FIRE RATINGS FOR |
| HORIZONTAL ASSEMBLIES PER FBC 711.1. |
| |
| 20) SPECIFY THE FIRE RATINGS OF WALL |
| ASSEMBLIES PER FBC 708.1. |
| |
| 21) SPECIFY THE FIRE RATINGS OF OPENING PROTECTIVES PER |
| FBC 715.1. THESE MAY BE |
| REQUIRED FOR EXTERIOR WALLS BASED ON |
| FIRE SEPARATION DISTANCE IN TABLE 704.8 |
| AND 704.12. |
| |
| 22) PROVIDE DETAILS OF THE RAISED |
| FLOORING. SPECIFY THE FIRE RATING OF THE |
| RAISED FLOOR SYSTEM. INDICATE HOW THE |
| REQUIRED FLOOR FIRE RATINGS WILL BE |
| MAINTAINED IN EGRESS CORRIDORS, ETC. |
| |
| 23) THE CORRIDORS ON THE FIRST FLOOR |
| THAT CONNECT THE EGRESS STAIRS TO THE |
| EXTERIOR EXIT DOORS SHOWN ON SHEETS A003 |
| AND A102 ARE CONSIDERED EXIT PASSAGEWAYS |
| PER FBC 1020. FBC 1020.3 REQUIRES THE |
| FIRE RATING TO BE NOT LESS THAN ANY |
| CONNECTING EXIT ENCLOSURE (WALLS, FLOORS |
| AND CEILING.). |
| |
| 24) EXIT PASSAGEWAYS MUST COMPLY WITH |
| FBC 1020.2 FOR WIDTH, WITH DOORS WHEN |
| FULLY OPEN NOT REDUCING THE REQUIRED |
| WIDTH BY 7" AND NOT REDUCING THE |
| REQUIRED WIDTH BY MORE THAN ONE-HALF |
| WHEN IN ANY POSITION. |
| |
| 25) EXIT PASSAGEWAYS TO COMPLY WITH FBC |
| 1020.4 OPENINGS AND PENETRATIONS. |
| EXIT PASSAGEWAY OPENING PROTECTIVES |
| SHALL BE IN ACCORDANCE WITH THE |
| REQUIREMENTS OF SECTION 715 . |
| EXCEPT AS PERMITTED IN SECTION 402.4.6 , |
| OPENINGS IN EXIT PASSAGEWAYS OTHER THAN |
| UNEXPOSED EXTERIOR OPENINGS SHALL BE |
| LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE EXIT PASSAGEWAY FROM |
| NORMALLY OCCUPIED SPACES AND FOR EGRESS |
| FROM THE EXIT PASSAGEWAY. WHERE INTERIOR |
| EXIT ENCLOSURES ARE EXTENDED TO THE |
| EXTERIOR OF A BUILDING BY AN EXIT |
| PASSAGEWAY, THE DOOR ASSEMBLY FROM THE |
| EXIT ENCLOSURE TO THE EXIT PASSAGEWAY |
| SHALL BE PROTECTED BY A FIRE DOOR |
| CONFORMING TO THE REQUIREMENTS IN |
| SECTION 715.3 . FIRE DOOR ASSEMBLIES IN |
| EXIT PASSAGEWAYS SHALL COMPLY WITH |
| SECTION 715.3.4 . |
| ELEVATORS SHALL NOT OPEN INTO AN EXIT |
| PASSAGEWAY. |
| |
| 26) FBC 1023.6 ACCESS TO A PUBLIC WAY. |
| THE EXIT DISCHARGE SHALL PROVIDE A |
| DIRECT AND UNOBSTRUCTED ACCESS TO A |
| PUBLIC WAY. |
| EXCEPTION: WHERE ACCESS TO A PUBLIC WAY |
| CANNOT BE PROVIDED, A SAFE DISPERSAL |
| AREA SHALL BE PROVIDED WHERE ALL OF THE |
| FOLLOWING ARE MET: |
| 1.THE AREA SHALL BE OF A SIZE TO |
| ACCOMMODATE AT LEAST 5 SQUARE FEET (0.28 |
| M 2 ) FOR EACH PERSON. |
| 2.THE AREA SHALL BE LOCATED ON THE |
| SAME PROPERTY AT LEAST 50 FEET (15 240 |
| MM) AWAY FROM THE BUILDING REQUIRING |
| EGRESS. |
| 3.THE AREA SHALL BE PERMANENTLY |
| MAINTAINED AND IDENTIFIED AS A SAFE |
| DISPERSAL AREA. |
| 4.THE AREA SHALL BE PROVIDED WITH A |
| SAFE AND UNOBSTRUCTED PATH OF TRAVEL |
| FROM THE BUILDING. |
| SHOW COMPLIANCE. |
| |
| 27) SPECIFY THE INTERIOR WALL AND |
| CEILING FINISH REQUIREMENTS PER FBC |
| 803.5. |
| |
| 28)FBC 3002.4 ELEVATOR CAR TO |
| ACCOMMODATE AMBULANCE STRETCHER. |
| IN BUILDINGS FOUR STORIES IN HEIGHT OR |
| MORE, AT LEAST ONE ELEVATOR SHALL BE |
| PROVIDED FOR FIRE DEPARTMENT EMERGENCY |
| ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR |
| SHALL BE OF SUCH A SIZE AND ARRANGEMENT |
| TO ACCOMMODATE A 24-INCH BY 76-INCH (610 |
| MM BY 1930 MM) AMBULANCE STRETCHER IN |
| THE HORIZONTAL, OPEN POSITION AND SHALL |
| BE IDENTIFIED BY THE INTERNATIONAL |
| SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| (STAR OF LIFE). THE SYMBOL SHALL NOT BE |
| LESS THAN 3 INCHES (76 MM) HIGH AND |
| SHALL BE PLACED INSIDE ON BOTH SIDES OF |
| THE HOISTWAY DOOR FRAME. |
| |
| 29) ELEVATORS SHALL COMPLY WITH |
| ACCESSIBILITY REQUIRES OF FBC 3007 AND |
| 11-4.10. |
| |
| 30) ALL REQUIRED EXITS ARE REQUIRED TO |
| BE ACCESSIBILE. SEE FBC 1007.1 AND 11-4.1.3(8)&(9). |
| SHOW COMPLIANCE. |
| |
| 31) SUBMIT ENGINEERED SHOP DRAWINGS FOR |
| THE ALUMINUM SUNSHADES. |
| |
| 32)FBC 1009.11.1 HEIGHT. |
| HANDRAIL HEIGHT, MEASURED ABOVE STAIR |
| TREAD NOSINGS, OR FINISH SURFACE OF RAMP |
| SLOPE SHALL BE UNIFORM, NOT LESS THAN 34 |
| INCHES (864 MM) AND NOT MORE THAN 38 |
| INCHES (965 MM). REVISE THE STAIR DETAIL |
| ON A408 TO SHOW MEASUREMENTS FROM THE |
| LEADING EDGE OF THE STAIR TREADS. |
| |
| 33) SHOW THE CURB RAMPS REQUIRED BY FBC |
| 11-4.7 AT THE ACCESSIBLE PARKING SPACES |
| ON THE ARCHITECTURAL DRAWINGS. |
| |
| 34) SPECIFY THE NUMBER OF ACCESSIBLE |
| PARKING SPACES AND THE TOTAL NUMBER OF |
| SPACES PROVIDED FOR EMPLOYEES AND |
| VISITORS. SEE FBC 11-4.1.2(5). |
| |
| 35)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| PRODUCT APPROVALS FOR EXTERIOR WINDOWS, |
| DOORS, ROOFING MATERIAL, ETC. |
| |
| 36) FBC*109.3.6 REQUIRES ALL PRODUCT |
| APPROVALS TO BE REVIEWED AND APPROVED BY |
| THE DESIGNER OF RECORD. |
| |
| 37) FBC 1609.1.4 REQUIRES EXTERIOR |
| GLAZING TO BE PROTECTED IN WINDBOURNE |
| DEBRIS REGIONS. SPECIFY HOW THIS WILL BE PROVIDED. |
| |
| 38) THE VALUE OF THE PROJECT HAS BEEN |
| INCREASED TO 70 PERCENT OF THE |
| CALCULATED VALUE. ($9,289,897.00) |
| |
| 39) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| 40) ALSO SEE HANDWRITTEN NOTES AND |
| CORRECTIONS ON THE PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |