2005-12-29 00:00:00 | *** DENIED *** |
| 1) PLANS ARE DIFFICULT TO READ. |
| CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 |
| . |
| |
| 2) ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. PER |
| FBC 104.2.1 . |
| |
| 3) PLEASE SUBMIT A MANUAL J CALCULATION, |
| PER 2004 FBC 13-607.1.ABC.1 . |
| |
| 4) PLEASE LIST AHU MODEL NUMBER ON |
| PLANS. |
| |
| 5) PLANS ARE SHOWING TWO AHU, IF YOU ARE |
| NOT INSTALLING TWO, PLEASE ONLY SHOW ONE |
| ON PLANS. |
| |
| 6) PLEASE NOTE THIS HOUSE IS BEING |
| RENOVATED AND IS NOT LISTED AS |
| HISTORICAL, AND MUST COMPLY WITH FBC'S. |
| |
| 7) PLEASE SUPPLY BALANCED RETURN AIR, |
| SEE NOTE 8). |
| |
| 8) BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |
| |
| |
| |
| |