Plan Review Notes For Permit 05121171 |
Permit Number |
05121171 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-20 00:00:00 | DENIED | | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | 1) FBC-2001424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. (DETAIL WITH MODEL NUMBER | | OF PRESSURE CLEANER FITTING REQUIRED) | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|