Date Text
2005-12-30 00:00:00AS-BUILT DRAWING
 PLEASE NOTE, PLAN DOES NOT SPECIFY SIZE
 OF THE TRANSFER GRILLE.PER 2001 FMC
 601.4 EXCEPTION #2, RETURN TRANSFER
 GRILLE SHALL BE HAVE MINIMUM OF 50
 SQUARE INCHES PER 100 CFM OF SUPPLY AIR
 INTO THAT SPACE.
  