Date |
Text |
2006-01-04 00:00:00 | DENIED: |
| 1.RETURN AIR FROM BATHROOM AREAS SHALL |
| NOT BE RECIRCULATED PER 2004 FMC 407.1. |
| |
| 2.PLAN SHEET 7 OF 8 INDICATES 150 CFM |
| OF EXHAUST FROM THE MENS RESTROOM/SHOWER |
| AREA.PER 2004 FMC TABLE 403.3, A TOTAL |
| OF 200 CFM IS REQUIRED FROM THE MENS |
| ROOM. |
| |
| 3.PROVIDE MANUFACTURER INFORMATION OR |
| SPECIFICATIONS FOR THE EXHAUST FAN. |
| PLANS DOES NOT INDICATE IF THE EXHAUST |
| FAN IS NEW OR EXISTING. |
| |
| 4.PLAN SHEET 7 OF 8 INDICATES SUPPLY |
| AND RETURN AIR DUCT GOINX DOWN TO THE |
| 1ST FLOOR IN AN EXISTING OPENING. |
| PLEASE CLARIFY IF THIS PENETRATION IS |
| RATED.SHOW COMPLIANCE WITH 2004 FMC |
| 607.6.1 & 607.8 OR 607.6.3. |
| |
| 5.PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| TABLE 403.3. |
| |
| 6.PLAN SHEET 8 OF 8, DETAIL FOR THE |
| AHU SHOWS A "SAFE-T-SWITCH" ON THE |
| AUXILIARY DRAIN LINE.PLEASE INDICATE |
| IF THE AHU HAS A BOTTOM RETURN.PLEASE |
| INDICATE IF THE RETURN AIR IS A DUCTED |
| BOTTOM RETURN OR SHOW COMPLIANCE WITH |
| 2004 FMC 307.2.3. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |