Plan Review Notes
Plan Review Notes For Permit 05121117
Permit Number 05121117
Review Stop M
Sequence Number 2
Notes
Date Text
2006-01-04 00:00:00DENIED:
 1.RETURN AIR FROM BATHROOM AREAS SHALL
 NOT BE RECIRCULATED PER 2004 FMC 407.1.
  
 2.PLAN SHEET 7 OF 8 INDICATES 150 CFM
 OF EXHAUST FROM THE MENS RESTROOM/SHOWER
 AREA.PER 2004 FMC TABLE 403.3, A TOTAL
 OF 200 CFM IS REQUIRED FROM THE MENS
 ROOM.
  
 3.PROVIDE MANUFACTURER INFORMATION OR
 SPECIFICATIONS FOR THE EXHAUST FAN.
 PLANS DOES NOT INDICATE IF THE EXHAUST
 FAN IS NEW OR EXISTING.
  
 4.PLAN SHEET 7 OF 8 INDICATES SUPPLY
 AND RETURN AIR DUCT GOINX DOWN TO THE
 1ST FLOOR IN AN EXISTING OPENING.
 PLEASE CLARIFY IF THIS PENETRATION IS
 RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.6.1 & 607.8 OR 607.6.3.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.
  
 6.PLAN SHEET 8 OF 8, DETAIL FOR THE
 AHU SHOWS A "SAFE-T-SWITCH" ON THE
 AUXILIARY DRAIN LINE.PLEASE INDICATE
 IF THE AHU HAS A BOTTOM RETURN.PLEASE
 INDICATE IF THE RETURN AIR IS A DUCTED
 BOTTOM RETURN OR SHOW COMPLIANCE WITH
 2004 FMC 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved