Plan Review Notes For Permit 05121117 |
Permit Number |
05121117 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-03 00:00:00 | *** DENIED *** | | 1) RETURN AIR CAN NOT COME FROM A PUBLIC | | RESTROOM, PER 2004 FBC/M 407.1 . | | | | 2) PLEASE PROVIDE FOR SUPPLY VENTILATION | | AIR, PER 2004 FBC/M 403.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|