Plan Review Notes
Plan Review Notes For Permit 05121091
Permit Number 05121091
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 RESIDENTIAL
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT AS-1 CODE REFERENCED AS FBC-2001.
 CODE IN EFFECT IS FBC-2004. PLEASE
 DESIGN TO PRESENT CODE AND CHANGE
 REFERENCE.
 2. SHT A-1 KITCHEN SINK TO BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. A TURNING AREA IS REQUIRED.
 3. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 4. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 5. SHT A-2 ROOF PLAN. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FOOTAGE OF THE
 ROOF, AND INCLUDE 1/2 AREA OF ALL
 VERTICAL WALLS IN THE CALCULATIONS. SHOW
 THE LOCATIONS FOR SECONDARY ROOF DRAINS
 OR OVERFLOW SCUPPERS. SCUPPER DETAIL
 REFERENCED CALLS OUT DETAIL 1 SHT A-8.
 SHT A-8 NOT SUBMITTED. PLEASE CLARIFY.
 SECTIONS 106.1.1, 1106, 1107 AND ALL
 SUBSECTIONS. THE SIZING OF THE OVERFLOW
 SCUPPERS CAN NOT BE DETERMINED WITH
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE SHOW CALCULATIONS FOR OVERFLOW
 SCUPPERS ON PLANS PER SECTIONS 1101.7,
 1107.3 AND TABLE 1106.7.
 6. SHT A-2 WATER HEATERS FOR THE
 RESIDENTIAL UNITS ARE NOT SHOWN. PLEASE
 INDICATE THE LOCATIONS OF THE WATER
 HEATERS REQUIRED BY SECTIONS 607.1 AND
 2801.1.
 7. SHT P-1 THE AUTOMATIC CLOTHES WASHER
 FIXTURES SHALL CONNECT TO A BRANCH DRAIN
 OR DRAINAGE STACK A MINIMUM OF 3" IN
 DIAMETER. SECTION 406.3.
 8. SHTS P-1 & P-2 SOME SANITARY RISER
 PIPE SIZES DO NOT REFLECT THE PIPE SIZES
 SHOWN ON THE FLOOR PLAN PIPE LAYOUT.
 PLEASE CORRELATE RISER DIAGRAM SO THAT
 IT REFLECT THE PIPING LAYOUT. SECTION
 106.1.1.
 9. SHT P-2 SANITARY RISER DIAGRAM, A
 TRAP AND A STANDPIPE ARE REQUIRED AT THE
 WASH MACHINES. SECTIONS 1002.1 & 802.4.
 10. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. (ICE MAKER, DISH WASHER,
 AND WASH MACHINE). WATER HAMMER
 ARRESTORS TO BE LOCATED IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 11. SECOND SHEET P-2, WATER HEATER
 DETAIL, THERMAL EXPANSION CONTROL
 REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD.
 12. SECOND SHT P-2 EMERGENCY PAN DRAIN
 LINE DIAGRAM SHOWS PAN DRAINING INTO AN
 ABOVE GROUND HUB DRAIN. THIS IS NOT
 SHOWN ON THE SANT. RISER DIAGRAM.
 CORRELATE RISER WITH DETAIL. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]