Date |
Text |
2006-03-09 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 RESIDENTIAL |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT AS-1 CODE REFERENCED AS FBC-2001. |
| CODE IN EFFECT IS FBC-2004. PLEASE |
| DESIGN TO PRESENT CODE AND CHANGE |
| REFERENCE. |
| 2. SHT A-1 KITCHEN SINK TO BE |
| ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. A TURNING AREA IS REQUIRED. |
| 3. PER TABLE 403.1 A DRINKING FOUNTAIN |
| IS REQUIRED. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS AS WELL AS SECTION |
| 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| HAVE DIFFICULTY BENDING OR STOOPING. |
| 4. AN RPZV BACKFLOW IS REQUIRED ON THE |
| WATER SERVICE. SECTION 608.13.2. |
| 5. SHT A-2 ROOF PLAN. SUBMIT |
| CALCULATIONS FOR PRIMARY AND SECONDARY |
| ROOF DRAINS. SHOW SQUARE FOOTAGE OF THE |
| ROOF, AND INCLUDE 1/2 AREA OF ALL |
| VERTICAL WALLS IN THE CALCULATIONS. SHOW |
| THE LOCATIONS FOR SECONDARY ROOF DRAINS |
| OR OVERFLOW SCUPPERS. SCUPPER DETAIL |
| REFERENCED CALLS OUT DETAIL 1 SHT A-8. |
| SHT A-8 NOT SUBMITTED. PLEASE CLARIFY. |
| SECTIONS 106.1.1, 1106, 1107 AND ALL |
| SUBSECTIONS. THE SIZING OF THE OVERFLOW |
| SCUPPERS CAN NOT BE DETERMINED WITH |
| REFERENCE TO THE DEFLECTION OF THE ROOF. |
| PLEASE SHOW CALCULATIONS FOR OVERFLOW |
| SCUPPERS ON PLANS PER SECTIONS 1101.7, |
| 1107.3 AND TABLE 1106.7. |
| 6. SHT A-2 WATER HEATERS FOR THE |
| RESIDENTIAL UNITS ARE NOT SHOWN. PLEASE |
| INDICATE THE LOCATIONS OF THE WATER |
| HEATERS REQUIRED BY SECTIONS 607.1 AND |
| 2801.1. |
| 7. SHT P-1 THE AUTOMATIC CLOTHES WASHER |
| FIXTURES SHALL CONNECT TO A BRANCH DRAIN |
| OR DRAINAGE STACK A MINIMUM OF 3" IN |
| DIAMETER. SECTION 406.3. |
| 8. SHTS P-1 & P-2 SOME SANITARY RISER |
| PIPE SIZES DO NOT REFLECT THE PIPE SIZES |
| SHOWN ON THE FLOOR PLAN PIPE LAYOUT. |
| PLEASE CORRELATE RISER DIAGRAM SO THAT |
| IT REFLECT THE PIPING LAYOUT. SECTION |
| 106.1.1. |
| 9. SHT P-2 SANITARY RISER DIAGRAM, A |
| TRAP AND A STANDPIPE ARE REQUIRED AT THE |
| WASH MACHINES. SECTIONS 1002.1 & 802.4. |
| 10. SUBMIT A WATER ISOMETRIC RISER |
| DIAGRAM. SHOW ALL PIPE SIZES, VALVES, |
| AND WATER HAMMER ARRESTORS REQUIRED BY |
| SECTION 604.9. (ICE MAKER, DISH WASHER, |
| AND WASH MACHINE). WATER HAMMER |
| ARRESTORS TO BE LOCATED IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING. PDI-WH 201 |
| AND MANUF. INSTALLATION INSTRUCTIONS. |
| 11. SECOND SHEET P-2, WATER HEATER |
| DETAIL, THERMAL EXPANSION CONTROL |
| REQUIRED PER SECTION 607.3.2. INDICATE |
| METHOD. |
| 12. SECOND SHT P-2 EMERGENCY PAN DRAIN |
| LINE DIAGRAM SHOWS PAN DRAINING INTO AN |
| ABOVE GROUND HUB DRAIN. THIS IS NOT |
| SHOWN ON THE SANT. RISER DIAGRAM. |
| CORRELATE RISER WITH DETAIL. SECTION |
| 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |